SJC Home
Clearance Sheet M2024-002998*010

 Department IssuesSigned OffIntl
Informational

Plan Approved for underground fire main for Terrassa: 9 multifamily apartment (3-story)buildings and 1 Clubhouse/fitness building. 12"x12" tee, 12" gate valve, 12" to 10" reducer, 10" RPDA BNFP (Zurn: Model 375DA). Fire main increases back to a 12" main before teeing off and splitting into a 10" and 8" fire main. Fire main loop consists of 10" and 8" DR-18 line. 5 private fire hydrants. 10 Standalone FDC's with 5" Storz connections with 4' lines leading into building separate from the fire sprinkler line finishing 1' AFF. 10 total, 6" fire sprinkler lines leading into each building to finish 1' AFF.   

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: Stuart Schnellenberger 904-209-1778, SSchnellenberger@SJCFL.US

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

8/20/2024 sschnellenberger