Clearance Sheet M2024-001512

 Department IssuesSigned OffIntl

Plans for a 21 head NFPA 13D fire sprinkler system for a townhome unit for the aboveground 1'AFF only.  The riser is located in the garage, it is indicated that the riser will be enclosed by others maintain the riser at 40 degrees.  In addition it is indicated on the plans that all exterior piping will be insulated (backflow), and all valves will be locked in the open position.  This will all be verified at final.   


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

 

6/18/2024 PWebb