Plan reviewed for underground fire sprinkler line for 124 Arrowwood Dr.
Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: S. Schnellenberger 904-209-1778, SSchnellenberger@SJCFL.US
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.