| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for new 13d sprinkler system with 23 heads. Reviewed as using FFPC 8th edition effective January 1, 2024. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Reviewer: V.Vitori For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us. To schedule fire inspections call 827 6842 (automated system). Questions about inspections or resubmitting your plans call 209 1740x1.
NFPA 24 does not apply to 13d systems.
|
| |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 8th Ed.
|
| |
|
|
1) How will backflow and any other above ground pipe be maintained above 40degrees? 13d:9.1.2
NOTE: This is a 13d system therefore nfpa 24 does not apply. Therefore an underground permit does not get pulled as the underground piping only needs to follow standard utility requirements. The sprinkler review is the only way we can capture requirements from nfpa 13d. It is your job to ensure 13d is met for sprinkler review and the sprinkler final. I don't care who does this work but it needs to be called out on your plans and carried out prior to the final (just like your noted attic insulation by others and riser freeze protection by others).
|
| |
|
|
2) How will the sprinkler control valve(s) on the backflow be supervised? 13d:7.1.2
NOTE: This is a 13d system therefore nfpa 24 does not apply. Therefore an underground permit does not get pulled as the underground piping only needs to follow standard utility requirements. The sprinkler review is the only way we can capture requirements from nfpa 13d. It is your job to ensure 13d is met for sprinkler review and the sprinkler final. I don't care who does this work but it needs to be called out on your plans and carried out prior to the final (just like your noted attic insulation by others and riser freeze protection by others).
|
| |