| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for new 8,221 SF, Type VB(V(000)) Construction, Sprinkled 13 (Supervised), Fire alarm system throughout, HVLS Fan. Building consists of an Assembly, Business and Storage (mail box area), non-separated – Mixed Use.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC. Chapter 30 (New Apartments) and Chapter 42 (Storage – Vehicle).
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
----------------------
Wednesday, February 22, 2023 DF: Review of 1st Resubmittal.
|
| |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the Permit Center. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8". - Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)
|
| |
|
|
1) One (1) set of plans for fifteen (15) clearance sheets: M22-7860, M22-7860*1, M22-7860*2, M22-7860*3, M22-7860*4, M22-7860*5, M22-7860*5, M22-7860*6, M22-7860*7, M22-78690*8, M22-7860*9, M22-7860-10, M22/7860-11, M22-7860*12, M22-7860*16 & M22-78960*17.
This comment will not be signed off until ALL clearance sheets have all other comments addressed.
----------------------
Wednesday, February 22, 2023 DF: RTC: One set of plans will be provided for each of the (15) Clearance Sheets.
Wednesday, February 22, 2023 DF: Reviewer's Response: I am noting that the Plan Set contains all the building information for the 15 Clearance Sheets. Once ALL comment's for ALL Clearance Sheets have been completed and signed off only then, can I sign this comment off.
|
| |
|
|
2) The following clearance sheets were provided with the plan set along with other clearance sheets noted in comment #1. Plans Sheet CD-0.1 listed the following Deferred Submittals: Elevator, Signage, Fire Sprinkler System, Emergency Response KNOX Box (FailSafe) final location approval, Access Control System, Fire Alarm systems, Swimming Pool and fence and equipment, Vehicular gates.
They have been noted and HOLDS assigned to the individual clearance sheet as applicable.
----------------------
Wednesday, February 22, 2023 DF: RTC: These sheets will be submitted as deferred submittals during the construction phase.
|
2/22/2023
| dfeagle |
|
|
3) Received the following clearance sheets missing the permit applications and plan sets: M22-7860*13 (pool), M22-7860*14 (pergola), M22-7860*15 (underground LP tank), M22-7860*18 (wooden walkway), M22-7860*19 (entry gate #1), M22-7860*20 (entry gate #2), and M22-7860*21 (sales trailer).
Provide the building applications and plans for each clearance sheet OR remove them from this review and submit them separately.
----------------------
Wednesday, February 22, 2023 DF: RTC: These items are not part of the architectural permit set. These items are permitted under the civil/landscape package that was submitted separately.
Wednesday, February 22, 2023 DF: Reviewer's Response: The noted Clearance Sheets are no longer in the Resubmittal Packet. The above Clearance Sheets are required to be reviewed by the Fire Marshals Office and/or the Building Department for compliance with the Florida Fire Prevention Code and the Florida Building Code before issuance of Building or Fire Marshal Permits.
A hold for permit will be placed on the Clubhouse Permit for these Clearance Sheets to be submitted for review.
|
2/23/2023
| dfeagle |
|
Informational
|
4) The complex will be constructed in 9 phases per the DRC notes: Clubhouse in Phase 2, Building 100 in Phase 3 and Garage 500 in Phase 3B. Building 200 in Phase 4 and Maintenance Building in Phase 4B, Building 300 in Phase 5 and Garage 100 in Phase 5B and Garage 200 in Phase 5C, Building 400 in Phase 6 and Garage 300 in Phase 6B, Building 500 in Phase 7, Building 600 in Phase 8 and Building 700 in Phase 9 and Garage 400 in Phase 9B.
----------------------
Wednesday, February 22, 2023 DF: RTC: Please refer to the permitted civil package set for information on the construction phasing for this project.
|
2/23/2023
| dfeagle |
|
|
5) Sheets A8-3.1 and A8-3.2 appear to be the Clubhouse door schedule but is not identified as such. NO hardware set schedule provided, No door number identification provided in the schedule. (Sheet A8-1.1) 101:30.2.2.2 (7.2.1)
Provide the door AND hardware schedule with the equipment list including but not limited to the manufacturer and model of the hardware.
----------------------
Wednesday, February 22, 2023 DF: RTC: The door hardware schedules was clarified below: A) Added Door Hardware Schedule, B) Added Clubhouse Door Schedule.
Wednesday, February 22, 2023 DF: Reviewer's Response: Please identify on Sheet A1-4.1; the door number for the exterior door between the Game Room and The Fitness Room, Identify the exterior door on the left side of the Fitness Room. Check the set and remarks columns and verify which door will have access control and which doors will have panic "EXIT" hardware. Some doors with the same hardware set states exit device and/or access control do not show the same details as other doors with the same hardware set. Example: Hardware Set 15 and Hardware Set 15.
|
| |
|
|
6) The plans indicate the Clubhouse will not be protected by Fire Sprinklers. Based on the construction type, square footage and the water model provided during DRC, the available fire flow does not meet the required minimum fire flow of 2,500 GPM.
A NFPA 13 fire sprinkler system is required for this building. NFPA 1:Table 18.4.5.2.1
Indicate on the plans the Clubhouse will be protected with a fire sprinkler system.
----------------------
Wednesday, February 22, 2023 DF: RTC: Fire service and FDC line added to clubhouse on P1-41. Fire Protection Design Criteria and Florida Administrative Code 61G15-32.004 for Clubhouse added to P0-0.1.
Wednesday, February 22, 2023 DF: Reviewer's Response: I am unable to find Sheet P1-41 or any variation thereof for the Clubhouse. ALSO, Sheet P0-0.1 has not been updated. The original submitted sheet is still in the plan set and only addresses the Residential Dwelling Units and Corridors.
NOTE: No replaced "P" Sheets found in the "OLD" set of Sheets.
|
| |
|
|
7) Provide a Fire Protection Sheet(s) for this buildings fire sprinkler system (61G15-32.004).
An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. It is not a full set of shop drawing. FLORIDA ADMINISTRATIVE CODE 61G15-32.004
----------------------
Wednesday, February 22, 2023 DF: RTC: Fire Protection Design Criteria and Florida Administrative Code 61G15.32004 for Clubhouse added to P0-0.1.
Wednesday, February 22, 2023 DF: Reviewer's Response: See Reviewer's Response to comment #6's Response To Comments (RTC).
|
| |
|
|
8) Attic Area 4.1 on Sheet A2-4.1 is 3,239 SF. Permitted per area is 3,000 SF. 101:8.6.11
How do you intend to meet 101:8.6.11?
----------------------
Wednesday, February 22, 2023 DF: RTC The Sheet was updated to meet NFPA 101:8.6.11 below. Sheet A2-4.1 - Clubhouse - Roof Plans. Revision 2 Summary: A) Updated Attic Area. B) Added Attic Area.
|
2/22/2023
| dfeagle |
|
|
9) Emergency lighting is needed in the Women’s Room 1382, Back porch, and Front Porch.
----------------------
Wednesday, February 22, 2023 DF: RTC: Emergency Lighting has been added to the noted areas. See updated sheets for more information.
Wednesday, February 22, 2023 DF: Reviewer's Response: Sheet E1-4.2 (Lighting) has not been updated. Update Sheet E1-4.2.
NOTE: No replaced "E" Sheets found in the "OLD" set of Sheets.
|
| |
|
|
10) Sheet E1-4.1 in the “Key Notes” section indicates that a wall oven will be installed. 101:12.3.2.2
a) Provide manufacturer’s specification sheets for the oven,
b) Will there be any other cooking equipment such as a stove, fryers, griddles, etc.?
----------------------
Wednesday, February 22, 2023 DF: RTC: Note Removed. The is no Kitchen equipment located in Clubhouse.
Wednesday, February 22, 2023 DF: Reviewer's Response: Sheet E1-4.1 (Power) has not been updated. Update Sheet E1-4.1.
NOTE: No replaced "E" Sheets found in the "OLD" set of Sheets.
|
| |
|
|
11) Electrical Sheet E1-4.1 Panel C1 indicates there is a fire place (fire place igniter).
What type of fire place: Gas, wood, etc.?
Provide the manufacturer’s specification sheets, instillation document, etc..
----------------------
Wednesday, February 22, 2023 DF: RTC: Clubhouse will utilize a Dimplex X74" Electric Fire Place. Specification Sheets to be provided by others in the form of a submittal during the construction phase of this project.
Wednesday, February 22, 2023 DF: Reviewer's Response: Plumbing Sheet P1-4.1 indicates a Propane line from an outside buried propane tank to the Clubhouse Fire Place.
Either Update Sheet P1-4.1 to reflect the "Electric" Fire Place or provide the manufacturer make and model of the Propane Fire Place.
NOTE: Based on your request, a HOLD 105 (framing) Inspection will be placed on the permit for the Clubhouse.
|
| |
|
|
12) I was not able to locate the Carbon Monoxide (CO) detector in the area of the fire place. 101:12.3.4.4
If the fire place is of the wood burning or gas burning type show the location of the CO detector on the plans..
----------------------
Wednesday, February 22, 2023 DF: RTC: Carbon Monoxide detectors have been added to the Fire Place Area. Sse updated Sheets for more information.
Wednesday, February 22, 2023 DF: I am unable to find the CO detectors on any of the Electrical Sheets for the Clubhouse. Please point out where the CO detectors are located of add them to Clubhouse Electrical Sheet(s).
NOTE: No Clubhouse Electrical Sheets have been changed out and there were none found in the "OLD" sheets.
|
| |
|
|
13) Plans indicate that the special locking arrangements (access control) will be deferred submittal. Will there be any special locking arrangements that include sensor release of electrical locking systems Access-Control) (101:7.2.1.6.2)?
If yes, please note the restriction of use noted in 101:12.2.2.2.6. Please contact this reviewer for information regarding this type of locking arrangement..
----------------------
Wednesday, February 22, 2023 DF: RTC: The Special Locking arrangement do not include sensor release of electrical locking systems.
|
2/23/2023
| dfeagle |
|
|
14) The LSP (Egress Diagram Sheet E1-4.2 CD-4.1) and the electrical sheets “Exit Signs” must match. I do not see any exit signs on the LSP.
Add Exit signs to the LSP and ensure the LSP and Electrical sheets match.
----------------------
Wednesday, February 22, 2023 DF: RTC: Exit Signs have been added to match the Life Safety Plans.
Wednesday, February 22, 2023 DF: Reviewer's Response: In the Plan Set the Code Diagrams Sheets CD-1.1, CD-2.1, CD-3.1 and CD-4.1 (Clubhouse) appear to be the LSP Sheets. I am unable to find any Sheets marked Life Safety Plan.
Please point out the location of the LSP if different from Sheet CD-4.1. Update the LSP Sheets Exit Signs to match the corresponding Electrical Sheets Exit Signs so they both match.
|
| |
|
|
15) There is a very large fan in Fitness Room 1417. Is this fan a High Velocity Low Speed (HVLS) fan? NFPA 13:11.1.7.
----------------------
Wednesday, February 22, 2023 DF: RTC: The Fitness Room utilizes standard fans specified as Modern Forms - Hydra 120" diameter silver fan.
Wednesday, February 22, 2023 DF: Reviewer's Response: Per the manufacturer's Spec Sheet this fan is a HVLS fan.
High Volume Low Speed Fan. A ceiling fan that is approximately 6 ft (1.8 m) to 24 ft (7.3 m) in diameter with a rotational speed of approximately 30 to 70 revolutions per minute. NFPA 13:3.3.14
|
2/23/2023
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Air handlers with more than 2000 CFM are required to have duct smoke detectors. NOTE: If there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. (NFPA 90A:6.4.4.2) Where smoke detectors required by 6.4 are installed in a building not equipped with an approved fire alarm system as specified by 6.4.4.2, the following shall occur: 1. Smoke detector activation required by section 6.4 shall cause a visual signal and an audible signal at a normally occupied area. 2. Detector troubles shall be indicated visually or audibly in a normally occupied area identified as air duct
|
2/23/2023
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following: NFPA 101 7.9.2.3 (1) Failure of a public utility or other outside electrical power supply (2) Opening of a circuit breaker or fuse (3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities. NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2.
|
2/23/2023
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Buildings containing Fire Alarm Systems, Fire Sprinkler Systems, etc. and/or Security Systems that make it difficult to access the building in an emergency are required to have a Fail Safe box. NFPA 1:18.2.2.1
Please contact St Johns County Fire Rescue Secretary Dawn Lyons at 904-209-1712 for the correct order form.
|
2/23/2023
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Occupancy Sensor NFPA 101: 7.8.1.2.2 Unless prohibited by Chapters 11 through 43, automatic lighting control devices shall be permitted to temporarily turn off the illumination within the means of egress, provided that each lighting control device complies with all of the following: (1) In new installations, the lighting control device is listed. (2) The lighting control device is equipped to automatically energize the controlled lights upon loss of normal power and is evaluated for this purpose. (3) Illumination timers are provided and are set for a minimum 15-minute duration. (4) The lighting control device is activated by any occupant movement in the area served by the lighting units. (5) In new installations, the lighting control device is activated by activation of the building fire alarm system, if provided. (6) The lighting control device does not turn off any lights relied upon for activation of photoluminescent exit signs or path markers. (7) The lighting control device does not turn off any battery-equipped emergency luminaires, unit equipment, or exit signs.
Be Prepared to Show Compliance at the time of your Fire Alarm Final or Fire Final.
|
2/23/2023
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- Wall and ceiling finish will meet Class A or B. 101:12.3.3.2.
- Floor finish in egress corridors shall be Class II. 101:12.3.3.5.2.
- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:38.3.3.3.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.
|
2/23/2023
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system: - Fire alarm system - Fire sprinkler system (Supervised) - Fire underground - HOLD 109 INSP for FailSafe Box Locations - HOLD 109 INSP for Signage - HOLD 109 INSP for Special Locking Arrangements (Access Control) - HOLD 109 INSP for Pool / Fence / Pool Equipment - HOLD 109 INSP for Vehicular Gates #1 & 2 - HOLD 109 INSP for Underground LP Tank - HOLD 109 INSP for Pergola - HOLD 109 INSP for Wooden Walkway - HOLD 109 INSP for Sales Trailer - - - -
|
2/23/2023
| dfeagle |
|
|
NOTE:
If you would like to get together to go over the remaining open comments, please feel free to contact me to schedule a meeting.
My contact information is at the top of this report.
|
| |