1.  T12 Truss Bracing: Detail S2.1D detail 14 shows bracing that penetrates the tenant separation wall. Please revise the detail to terminate the bracing at the exterior of the drywall.


 

 
8/3/2011 jpaula

 2.  T16, T17, and T18: The interior bearing of T16, T17, and T18 occur in the tenant separation wall. Please revise the bearing to occur on the outside of the tenant separation wall.


 

 
8/3/2011 jpaula

 3.  Solatube: Please provide state product approval for the Solatube.


 

8/3/2011 jpaula

4. Energy Form: Please revise the energy form: (1)Indicate foam plastic at the attic roof deck. (2) Provide the ES report for foam plastic that is proposed and indicate which application will be used. (3) A separate energy form for each unit (FBC-R N1100.06) 

8/3/2011 jpaula

5.  Attic Truss Tenant Separation: The proposed tenant separation at the attic truss is incorporating the wall assembly U314. Please provide an assembly that has been tested with a roof truss or use the time assignment from FBC Table 721.6.2(1)