**Provide cut sheet for the FDC.
FDC connections on piping LARGER than 2 inches shall be equipped with a five (5) inch Storz connection and shall have a 30 degree downward deflection. In addition, there shall be a check valve at the head.
This applies to all FDCs regardless being on a standpipe, building or free standing. (NFPA 24:5.9.1.2, and 5.9.2.4)