Clearance Sheet C2026-003501

 Department IssuesSigned OffIntl

Plan reviewed for fire underground to 8" DCDA to serve 2 private FHs on 8" DR-18 fire main and 2 fire sprinkler lines on 6" DR-18 fire main. FDCs on 6" lines are freestanding and connect directly to fire risers.

Reviewed using FFPC 8th edition effective Dec. 31, 2023.

Reviewer: 
Stephanie Murray 904-209-1742 smurray@sjcfl.us  
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740 x 1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

**Provide cut sheet for the FDC.

FDC connections on piping LARGER than 2 inches shall be equipped with a five (5) inch Storz connection and shall have a 30 degree downward deflection. In addition, there shall be a check valve at the head.

This applies to all FDCs regardless being on a standpipe, building or free standing. (NFPA 24:5.9.1.2, and 5.9.2.4)

 

The required backflow preventer is required to be electronically monitored by the fire alarm panel.
This is achieved by placement of tamper switches on OS&Y valves on top of BFP. While the Fire Alarm contractor will take care of this, during the underground review, a note on the underground fire main plan stating the Fire underground contractor will coordinate the placement of conduit during the installation the underground fire main from the BFP to the building that will house the fire alarm panel with the site contractor or fire alarm contractor. If conduit isn't installed at this stage, it will require trench cutting of new asphalt or concrete. 

 

**Provide cut sheet for how the Backflow will be protected from freezing.