Plan submitted for new 6'3" Stratovent hood, Stratovent exhaust fan, and unknown duct type. Reviewed as using FFPC 8th edition effective January 1, 2024. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

The print is so small on these 8x11 pages it is very hard to read.

Monday, November 9, 2026 Only 1 set of responses, plans and specs provided. Plans will be stamped "office copy". To acquire a second job copy, wait til plans are approved and scanned. Then you can get a reprint from County Records.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed. NFPA 1:1.12.4</span

 

1) Hood and suppression plans don't match. Previously approved suppression plans are protecting a 48" hood. This hood submittal shows a 6'3" hood. Update/revise the incorrect plan. 1:1.14

NOTE: This hood plan will not be approved until either this submittal matches the suppression of 48" or the suppression plan is revised showing a 6'3" hood.

Monday, November 9, 2026 Response to comment indicates "The hood size is 6'3" per plans and hood shop drawings. My fire suppression vendor (Fire House Safety Solution/ Tim Nguyen 904-449-6697) spoke with plans reviewer about correcting the Fire Suppression permit and he was advised by Mr. Webb (plans examiner) on 11/2 that as long as its under 10' then we will be fine and do not need to correct this typo. He will be submitting a letter under the Fire Suppression permit #62600461 explaining this error and confirming that they do match."

On 11/2 plan reviewer Webb did speak with me following the phone call. He acknowledged that the suppression permit is wrong.

11/9/2026 VVitori

2) Show cooking equipment layout (13:1.2) and provide spec sheet showing listing of each appliance (96:13.1).

Monday, November 9, 2026 Response to comment indicates "A2.0 Equipment Plan and A2.1 Equipment Schedule were printed and submitted with revised permit application."

11/9/2026 VVitori

3) If any of the cooking appliances are on casters what is the method that is to be used to ensure that the appliance is returned to the approved design location? 96:13.1.2.3.1

Monday, November 9, 2026 Response to comment indicates "The rethermalizer will have rails installed that guide the equipment back to its initial location per A6.0/7. The Fryer will have wheel chalks installed.. Included with this revision is the specification sheet for equipment on casters."

11/9/2026 VVitori

4) Sheet 1 does not indicate wall construction/type to check compliance with 96:4 for clearances. It looks like plan shows that Stratovent hood has a clearance reduction system provided only behind the hood.

Either:

a) provide listing spec sheet for Stratovent to show clearance reduction system and update plans that it will be provided all the way to the floor (96:4.2.4.3) OR

b) show wall construction/type that meets the clearances called out in 96:4.

Monday, November 9, 2026 Response to comment indicates "W-5 - 2x6 5.5" metal studs with 20 GA SS panel over cement board extended 18" beyond each side. Please refer to the included A1.0 Floor Plan wall type legend for reference."

11/9/2026 VVitori

5) Unable to locate how combustible clearances to ducts will be maintained. Show compliance with 96:4.

Monday, November 9, 2026 Response to comment indicates "Compliance is shown on provided sheet M4.0/10."

2 layers Firemaster Blanket.

11/9/2026 VVitori

6) Unable to locate duct details that show compliance with 96:7. Show compliance with 96:7.

Monday, November 9, 2026 Response to comment indicates "Compliance shown on provided sheet M4.0/10."

Looking at M4.0/11 it is a straight shot and do not see anything saying it is a listed assembly. Call out compliance with:

a) Duct material. 96:7.5.1

 

 

7) Unable to locate listing for "SS baffle with handles L55 series E26" when I search the internet. Provide manufacturer spec sheets showing baffle filter listing. 96:6.1

Monday, November 9, 2026 Response to comment indicates "Specifications on baffle filters are included in this revision. As UO files are proprietary, a copy of the actual fire is not publicaly available. The cut sheet does note they are UL1046 that is under File Number R7349. The comments about the l55 Series E26 is from the hood light fixtures, not the grease filters. Grease filters are Kleen Gard, 15.625" H x 15.625"W."

11/9/2026 VVitori

8) Unable to check rooftop termination in accord with 96:7.8.2. Show detail so it can be checked.

Monday, November 9, 2026 Response to comment indicates "Detail can be found on provided sheet M3.0/1."

Unable to locate where all of the following are illustrated:

a) 10' of horizontal clearances from outlet to air intakes. 96:7.8.1.2.(1)

b)  5' of horizontal clearance from fan housing to any combustible structure. 96:7.8.1.2(2)

c) vertical separation of 3' above any air intakes within 10' of exhaust outlet. 96:7.8.1.2(3)

d) exhaust grease collection system is UL710a listed. 96:7.8.1.2(6)

e) flexible weatherproof electrical cable. 96:7.8.1.2(8)