Plan submitted for new 6'3" Stratovent hood, Stratovent exhaust fan, and unknown duct type. Reviewed as using FFPC 8th edition effective January 1, 2024. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

The print is so small on these 8x11 pages it is very hard to read.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed. NFPA 1:1.12.4</span

 

1) Hood and suppression plans don't match. Previously approved suppression plans are protecting a 48" hood. This hood submittal shows a 6'3" hood. Update/revise the incorrect plan. 1:1.14

NOTE: This hood plan will not be approved until either this submittal matches the suppression of 48" or the suppression plan is revised showing a 6'3" hood.

 

2) Show cooking equipment layout (13:1.2) and provide spec sheet showing listing of each appliance (96:13.1).

 

3) If any of the cooking appliances are on casters what is the method that is to be used to ensure that the appliance is returned to the approved design location? 96:13.1.2.3.1

 

4) Sheet 1 does not indicate wall construction/type to check compliance with 96:4 for clearances. It looks like plan shows that Stratovent hood has a clearance reduction system provided only behind the hood.

Either:

a) provide listing spec sheet for Stratovent to show clearance reduction system and update plans that it will be provided all the way to the floor (96:4.2.4.3) OR

b) show wall construction/type that meets the clearances called out in 96:4.

 

5) Unable to locate how combustible clearances to ducts will be maintained. Show compliance with 96:4.

 

6) Unable to locate duct details that show compliance with 96:7. Show compliance with 96:7.

 

7) Unable to locate listing for "SS baffle with handles L55 series E26" when I search the internet. Provide manufacturer spec sheets showing baffle filter listing. 96:6.1

 

8) Unable to check rooftop termination in accord with 96:7.8.2. Show detail so it can be checked.