SJC Home
Clearance Sheet C2025-002515

 Department IssuesSigned OffIntl

Plan reviewed for a minor revision to the electrical pages of approved permit # 12508954. Scope is limited to the service size being downgraded.

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: J.L. Hatcher 904-209-1741, jlhatcher@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

12/29/2025 jlhatcher