Plans for a single Westell BDA (DAS) system for both the emergency room building and the medical office building.  Per the contractor, the control unit will be installed in whichever building progresses first.  In conversation with the contractor the system is deigned to for the control unit to be in either. The donor antennae will be located on the roof of the ER building.  


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

4/1/2025 PWebb

1) A revision is required to update the plans with the final location of the control unit and the annunciators.  Annunciators must be located near the main entrance/exit to the MOB building and at the security area of the ER building.  A hold has been placed on the permit for this revision. 