Clearance Sheet C2024-004009 |
|
| Department Issues | Signed Off | Intl |
|
Plan reviewed for New 358,814 SF Type IB(II(222)) Construction, Sprinkled (Wet-Interior and Dry-Parking Garage), Fire Pump, Standpipes; Class 1-Wet, Pool on Level 3, Total building height: 52’-8”. Fire Alarm w/Voice Evac, Horizontal ExitS – 3rd Floor.
Level 1; 116,374 SF, Level 2; 67,042 SF, Level 3; 103,760 SF, Level 4; 72,116 SF.
Multiple Occupancy - Mixed Use: Assembly, Mercantile, Business, Storage, Storage-Enclosed Parking Garage.
Horizontal Exits are utilized from Compartment "A" Only.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
----------------------------
Tuesday, August 6, 2024 DF: Review of 1st Resubmittal.
|
| |
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 7th Ed.
|
| |
|
1) This is a preliminary review. Do not resubmit until clearance sheet and approved site plan obtained. Turn in both clearance sheet and approved site plan with building permit application to Fire Permit Tech.
NOTE: Based on fire's site review, additional comments may be provided.
|
8/7/2024
| dfeagle |
|
1a) Design approach noted on Sheet G0.03 indicates Mixed use approach; Nonseparated use (occupancies). Per 101:6.1.14.3.2, The most restrictive requirements of the occupancies involved shall be used throughout the building.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Response to 1a &12: A complete 2-hour fire barrier separation will be provided between the S-2 Parking Garage and the rest of the building on all levels. The design approach is separated mixed use (S-2 separated from A-2 / A-3 / B/M) and will comply with the most restrictive requirements for the occupancy therein.
Drawing Sheets Impacted: G1.01, G1.02, G1.03, and G1.04 [center of plans and throughout], as well as respective A1.0# and A2.0# Sheets. Walls between Parking Garage and the rest of the building are clarified to have a 2-hour fire rating and doors to have a 90-minute fire rating, typically.
---------------------------
Wednesday, August 7, 2024 DF: Reviewer's Response: The Florida Fire Prevention Code 7th Ed. (FFPC) does not provide a classification of "Separated Mixed Use". Multiple occupancies within a building are either Separated Occupancies or they are Mixed Occupancies [101:6.1.14.2.2, 6.1.14.4]. A Separated Occupancy shall be completely separated from other occupancies. This includes the separated occupancy's means of egresses [101:6.1.14.4.1]. As the occupancies in both Compartment A and Compartment B utilize Horizontal Exits to both compartments as a part of their means of egress, the most restrictive Occupancy applies throughout.
|
| |
|
2) Rolls containing Sheets Lax.xx contain the outside landscaping, Lighting, Irrigation, etc. The plans also contain some pool information pertaining to the landscaping. The Landscaping Sheets are a part of the Civil Review and not a part of the building review. Any information inside the Lax.xx Sheets that are a part of the building review need to be integrated with the construction Sheets as necessary to be reviewed. Remove all other Sheets not pertaining to the building.
----------------------------
Tuesday, August 6, 2024 DF: RTC: All Landscaping, Lighting, and Irrigation Sheets not pertaining to the building review have been removed.
|
8/7/2024
| dfeagle |
|
3) Section 4.8 on Sheet G0.03 references Table 28.3.2.2.3 regarding storage room hazard protection. The Table noted above is in the New Hotel Chapter oF NFPA 101. I did not see any Hotel Occupancy in this plan set.
Correct the table to be quoted.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Hotel Occupancy is not a part of the project. G0.03 has been revised and clouded to remove references to Hotel Occupancy. [Upper Center of Sheet.]
|
8/7/2024
| dfeagle |
|
4) Sheet A7.10: Detail K1 has 2012 ED. Of the Life Safety Code (LSC) noted. Needs to be the 2018 ED.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Note has been revised and clouded on A7.10. [Upper Left of Sheet.]
|
8/7/2024
| dfeagle |
|
5) In Building Radio Enhancement System (BDA) See also FS633.202(18)
This building is required to have a third-party contractor conduct a two-way radio communication test in accordance with NFPA 1:11.10 and NFPA 1225 (2022 ED.) before the 105-framing inspection. St Johns County Fire Rescue’s radio control frequency is 853.8875.
-If it passes the inspection radio testing, you will need to submit a copy of the testing results as a revision so we can record the documentation and remove the hold.
- If the third-party paperwork indicates the test is not satisfactory, then the contractor will have to submit for a revision. The revision will need to include: the unsatisfactory test paperwork, outline of corrective measures, and plans to illustrate the corrective measures to meet requirements provided by the design professional.
At the final, you will be required to provide satisfactory testing by the third-party contractor following the installation of the in-building radio enhancement system.
----------------------------
Tuesday, August 6, 2024 DF: RTC: BDA testing note added to Sheet E0.00. [Center Right of Sheet.]
Wednesday, August 7, 2024 DF: Reviewer's Response: Newly added BDA Note calls out "IFC Section 510...". SJCFMO uses NFPA 1225 2022 ED.
Update the BDA Testing Note to reflect NFPA 1225 and it's requirements.
|
| |
|
6) The FP Sheets do not contain the 61G15-32.004 information and are not signed and sealed by the Engineer. FAC 61G15-32.004
Have the engineer update the FP Sheets with the 61G15-32.004 information and wet sign and wet seal the FP Sheets.
----------------------------
Tuesday, August 6, 2024 DF: RTC: FAC 61G15-32.004 information added to [top left corner] FP1.01. Full set of plans have been signed and sealed.
Tuesday, August 6, 2024 DF: Reviewer's Response: Sheets FP1.01, FP1.02, FP1.03, FP1.04, and FP1.05 have been Digitally Sealed by EOR Christopher Lyles. The Digital Signature states: "Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies." I am not able to verify the signature.
Provide the documents with a "Wet Seal" and a "Wet Signature".
|
| |
|
7) The Life Safety Sheets (“Means of Egress Plan”) Do not clearly show the exterior ways of the exit, exit discharge to the public way from inside the building. For example: discharge from Stair #4 and #5, How do I get to the public way? From the Tennis Shop to the Public Way and Stairs #2 and #3, Same scenario.
Provide a means of egress Sheet(s) showing the exterior routes from the exits of the building.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Sheet G1.01 [throughout] has been revised floor plan to include dashed lines and arrows to show the exterior ways of the exit, exit discharge to Public Way from inside the building. Site context, including sidewalks, hardscape, and low navigable landscape has been graphically depicted. A note describing the landscape design intent within a hatched area has been added top-left of plan.
|
8/8/2024
| dfeagle |
|
8) Life Safety Sheets (Means of Egress Plans), I do not see any exit signage on the LSP Sheets. The LSP Sheets and the Electrical Sheets must match the EXIT sign locations. This is so I can verify means of egress requirements.
Update the LSP sheets so they match the Electrical Sheets.
NOTE: There are egress comments noted below in this submittal review that are based on what I am able to determine is egress routes. However, upon review of the to be forthcoming 1st Resubmittal, there may be additional comments based on egress.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Life Safety Sheets G1.01, G1.02, G1.03 and G1.04 have been updated throughout to depict exit signage. Electrical Sheets match signage location respectively. [Throughout Sheets.]
|
8/8/2024
| dfeagle |
|
9) Plans show 4 Levels (floors): 4 story enclosed parking garage, 3 occupied levels and two large mechanical rooms on the roof. The 2nd Level (floor) identifies the 2nd Level enclosed parking garage but does not identify the space between the 1st Level and 3rd Level. The plans appear to indicate that there are some floor areas on level 2. For example; Sheet A5.03 above the Fire Pump Room, Daycare, Trash Holding area, etc.
a) Are these spaces utilized for access to equipment (mechanical, pool, electrical, plumbing, storage, etc.?
b) How do you access these spaces?
c) Point out the areas and code references for egress allowances, exceptions.
----------------------------
Tuesday, August 6, 2024 DF: RTC: A more accurate description of the design intent is a 4 story parking garage, 2 occupied levels, and 2 large mechanical rooms on the roof.
To clarify, aside from the enclosed parking garage (generally the footprint of Compartment B), there is not accessible or occupiable space between the 1st level and 3rd level. This intention is illustrated on A1.02, A2.02A, and A2.02C as a diagonal hatch with the text note "SPORTS CLUB LEVEL 1 BELOW". To further clarify in response to this Review Comment 9, the same diagonal hatch and note has been applied to G1.02 [throughout plan.].
The section views on A5.03 also support this design intent. To be clear, the Fire Pump Room and the Trash Holding area are within the footprint of the garage and simply have the next level parking above it, depicted in the section views B16 and K1 as a concrete-hatched floor slab (Level 2).
Additional text notes and room tags have been added and clouded to section views clarify spaces above Level 1. As section view K7 on Sheet A5.02 illustrates, there is not an occupiable floor slab above the Childcare room until Level 3, with only a ceiling and non-occupiable mechanical space in between.
|
8/13/2024
| dfeagle |
|
10) Outside of the Mechanical Rooms on the roof, will any of the roof be utilized for any other activities or occupancies?
----------------------------
Tuesday, August 6, 2024 DF: RTC: No other activities or occupancies are intended outside of the Mechanical Rooms on the roof.
|
8/8/2024
| dfeagle |
|
11) Sheets G1.01, G1.02, G1.03 and G1.04 provide an “Occupant Load Schedules” based on FBC. I do not see a parallel FFPC reference on these Sheets.
Provide the parallel/matching FFPC Occupant Load references.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Life Safety Sheets G1.01, G1.02, G1.03, and G1.04 have been revised to provide parallel/matching FFPC Occupant Loads, [Left and Lower Left of Sheets].
|
8/13/2024
| dfeagle |
|
12) The plans call for Mixed Use, Nonseparated use (occupancies). I see separation primarily on the 3rd Level. Please explain the separated use in this and other areas if the intent is mixed use – nonseparated use.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Response to 1a &12: A complete 2-hour fire barrier separation will be provided between the S-2 Parking Garage and the rest of the building on all levels. The design approach is separated mixed use (S-2 separated from A-2 / A-3 / B/M) and will comply with the most restrictive requirements for the occupancy therein.
Drawing Sheets Impacted: G1.01, G1.02, G1.03, and G1.04 [center of plans and throughout], as well as respective A1.0# and A2.0# Sheets. Walls between Parking Garage and the rest of the building are clarified to have a 2-hour fire rating and doors to have a 90-minute fire rating, typically.
Thursday, August 8, 2024 DF: Reviewer's Response: The Florida Fire Prevention Code 7th Ed. (FFPC) does not provide a classification of "Separated Mixed Use". Multiple occupancies within a building are either Separated Occupancies or they are Mixed Occupancies [101:6.1.14.2.2, 6.1.14.4]. A Separated Occupancy shall be completely separated from other occupancies. This includes the separated occupancy's means of egresses [101:6.1.14.4.1]. As the occupancies in both Compartment A and Compartment B utilize Horizontal Exits to both compartments as a part of their means of egress, the most restrictive Occupancy applies throughout.
|
8/8/2024
| dfeagle |
|
13) Plans call out “Exit Access Stair with Partial Enclosure in accordance with FFPC §8.6.8” (Sheet G1.03). See note on Sheet G1.03 and Code Summary 4.5 on Sheet G0.03.
NFPA 101:8.6.8 “Two-Story Openings with Partial Enclosure” does not apply to the Grand Stair opening as the opening spans more than two (2) adjacent stories. The Grand Stair opening spans three (3) stories in total.
Demonstrate compliance with Vertical Openings ~ 101:12.3.1.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Response to Comments 13 & 15: A 2-hour fire barrier completely separates the garage from the rest of the building. Per NFPA 101:8.2.2.2, fire barriers create separate fire compartments. Note that, the 2-hour fire barrier serves as a horizontal exit for the Assembly area on Level 3 as permitted by NFPA 101:12.2.2.5. Further commentary of the horizontal exit section states that; each area is a fire compartment independent of the other compartment. When looking at the two separate compartments, the garage fire compartment is 4 levels, while the rest of the buildings' fire compartment is 2 Levels. By creating these separate compartments, the Grand Stair opening is only spanning two adjacent stories.
As permitted by NFPA 101:12.3.1, the vertical opening is separated by a 2-hour separation on the upper level.
Drawing Sheets Impacted: G1.01, G1.02, G1.03, and G1.04 [center and throughout], as well as respective A1.0# and A2.0# Sheets. Walls between Parking Garage and the rest of the building are clarified to have a 2-hour fire rating and doors to have a 90-minute fire rating, typically.
Thursday, August 8, 2024 DF: Reviewer's Response:
Thursday, August 8, 2024 DF: Reviewer's Response: The RTC provided explains the separation of the Parking Garage and the remainder of the building into two separate Fire Compartments. However, this does not address the vertical openings [Grand Stair and adjacent vertical opening] meeting 101:12.3.1.
NOTE on Sheet G1.03 states; “We are regulating the Grand Stair as an Exit Access Stair…” The Grand Stair by the discerptions provided [throughout the Plan] is a convenience stair. Per 101:12.3.1(4) / 101:8.6.9.2(1) “The convenience openings shall not serve as required means of egress”. Exit Access is a portion of a means of egress that leads to an exit [101:3.3.87]. In this plan set I do not see any Exit Signage directing egress to the Grand Stair. The Vertical opening appears to meet 101:12.3.1(3) and, the Grand Stair appear to meet 101:12.3.1(4).
|
8/8/2024
| dfeagle |
|
14) One of the pool egress routes utilizes the Grand Stair as a means of egress (Sheet G1.03). The Grand Stairs is not a permitted means of egress (see comment above regarding 101:8.6.8 above). 101:12.2.4.4
Provide an updated LSP demonstrating the 2nd means of egress from the Pool Area.
----------------------------
Tuesday, August 6, 2024 DF: RTC: NFPA 101:8.6.8 commentary permits the Grand Stair to be used for exit access, just not and exit. The pool and other areas meet travel distance to other exits on the floor. Refer to response to comment 13 & 15.
Thursday, August 8, 2024 DF: Reviewer's Response: See Reviewer's Response to Comments 13 & 15 regarding the use of the Grand Stair as an Exit Access. NOTE: The second means of egress from the pool is directed to Stair 1 bypassing the Grand Stair.
|
8/8/2024
| dfeagle |
|
15) There is a vertical opening spanning from the 1st floor to the 3rd floor by the Grand Stair elevator. 101:12.3.1
Demonstrate how you will meet the vertical opening requirement of 101:12.3.1.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Response to Comments 13 & 15: A 2-hour fire barrier completely separates the garage from the rest of the building. Per NFPA 101:8.2.2.2, fire barriers create separate fire compartments. Note that, the 2-hour fire barrier serves as a horizontal exit for the Assembly area on Level 3 as permitted by NFPA 101:12.2.2.5. Further commentary of the horizontal exit section states that; each area is a fire compartment independent of the other compartment. When looking at the two separate compartments, the garage fire compartment is 4 levels, while the rest of the buildings' fire compartment is 2 Levels. By creating these separate compartments, the Grand Stair opening is only spanning two adjacent stories.
As permitted by NFPA 101:12.3.1, the vertical opening is separated by a 2-hour separation on the upper level.
Drawing Sheets Impacted: G1.01, G1.02, G1.03, and G1.04 [center and throughout], as well as respective A1.0# and A2.0# Sheets. Walls between Parking Garage and the rest of the building are clarified to have a 2-hour fire rating and doors to have a 90-minute fire rating, typically.
Thursday, August 8, 2024 DF: Reviewer's Response: The RTC provided explains the separation of the Parking Garage and the remainder of the building into two separate Fire Compartments. However, this does not address the vertical openings [Grand Stair and adjacent vertical opening] meeting 101:12.3.1.
NOTE on Sheet G1.03 states; “We are regulating the Grand Stair as an Exit Access Stair…” The Grand Stair by the discerptions provided [throughout the Plan] is a convenience stair. Per 101:12.3.1(4) / 101:8.6.9.2(1) “The convenience openings shall not serve as required means of egress”. Exit Access is a portion of a means of egress that leads to an exit [101:3.3.87]. In this plan set I do not see any Exit Signage directing egress to the Grand Stair. The Vertical opening appears to meet 101:12.3.1(3) and, the Grand Stair appear to meet 101:12.3.1(4).
|
8/8/2024
| dfeagle |
|
16) Exercise Rooms: Group Fitness 127, Mind-Body Studio 123, Pilates Group 119, Group waiting 129, Spin 125, Pilates Personalized 121, and Possibly Mind-Body Sanctuary 118 (need more detail as to activity) were calculated at 50sf per occupant (15sf per occ for Group waiting). 101:7.3.1.2 uses this the calculation of 50sf for exercise rooms with equipment. These rooms do not have equipment shown or only a few pieces which does not fill the majority of the room. The occupant load factor for each of the listed rooms would be 15. 101:6.1.14.3.2
The adjusted calculation for each exercise room would be: Group Fitness 127 (143 occ), Mind-Body Studio 123 (88 occ), Pilates Group 119 (76 occ), Group Waiting 129 (86 occ (601/7sf), Spin 125 (76 occ), Pilates Personalized 121 (75 occ), and Mind-Body Sanctuary 118 (48 occ).
a) Adjust the occupant loads for each room and provide for correct number of means of egress for each.
b) Adjust the Door and Hardware schedules where necessary for Panic Hardware where the occupant load is over 100.
----------------------------
Tuesday, August 6, 2024 DF: RTC: The occupant loads for each of the rooms outlined in the submittal review Comment #16 has been updated to with an occupant load factor of 15 sf/ per occupant. Notes have been added clarifying that the Group Waiting and Mind Body Sanctuary are waiting areas with seating, graphically depicted as a long bench and circular furniture respectfully. The door schedule on A9.10 has been revised to reflect the updated occupant loads. the column on the schedule that indicates panic hardware is 10th from the right. [Sheet G1.01, mostly Left of plan and Occupancy Load Schedules on left of Sheet.]
|
8/8/2024
| dfeagle |
|
17) GYM (OPEN PLAN): This room has something spread loosely about the room. The symbol does not appear to be anything I have seen or recognize as exercise equipment. Provide the symbols for the correct exercise equipment in their location and/or provide an occupant load based on 15. 101:6.1.14.3.2
----------------------------
Tuesday, August 6, 2024 DF: RTC: Plans have been revised to show the exercise equipment in their locations. Sheets G1.03, A1.03, A2.03A, and A2.03C [Equipment depicted graphically throughout plans].
|
8/8/2024
| dfeagle |
|
18) The following rooms need additional Exits 101:12.2.4: Group Fitness 127, Group Waiting 129, Spin 125, Pilates Personalized 121. 101:12.2.4
Show additional Exits for these rooms.
----------------------------
Tuesday, August 6, 2024 DF: RTC: The plan on G1.01 have been updated with symbols and dimensional lines to demonstrate at least two exits with sufficient exit separation distance. [Left side of plans.]
Thursday, August 8, 2024 DF: Reviewer's Response: Spin 125 has both of it's Exits opening into the same room [Group Waiting 129]. Pilates Personalized 121 has both of it's Exits opening into the same room [Mind Body Sanctuary 118]. The exits in the rooms meet the remoteness. However, the egress paths are comingled in the adjacent rooms and do not meet the code or intent of remoteness. 101:7.5.1.3.1
* Spin 125 and Pilates Personalized 121 will need to have their exits adjusted so that both of their egress paths do not open into the same room / use the same paths.
* Group Waiting 129 will need to have two separate means of egresses to accommodate Spin 125 occupants plus Group Waiting 129's occupants. Currently the doors from Group Fitness open in the wrong direction and no exit signage over the door to Group Fitness.
* Mind and Body Sanctuary 118 will need to have two separate means of egresses to accommodate Pilates Personalized 121 occupants plus Mind and Body Sanctuary's 118 occupants plus Pilates Group 119 occupants. Currently the doors from Pilates Group 119 open the wrong direction to and there is no Exit sign.
|
| |
|
19) The following rooms have the two Exits. However, the Exits do not meet the remoteness requirement of 101:7.5.1.3.1 measured from nearest edge of the exits (101:7.5.1.3):
Mind-Body Studio 118, Pilates Group 119.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Plan on Sheet G1.01 has been revised with symbols and dimensional lines to demonstrate the remoteness of the Exits for the Mind-Body Studio 118 and Pilates Group 119, which exit to the "Mind Body Sanctuary" which functions as a pre-function for the exercise spaces. [Left side of plans.]
Thursday, August 8, 2024 DF: Reviewer's Response: The remoteness lines on the plans are drawn from center of door to center of door. The remoteness is to be measured from closest door frame edge to closest door frame edge. 101:7.5.1.3.2
Check the plans, adjust remoteness as needed.
|
| |
|
20) Dead-End Corridors greater than 20’: 101:12.2.5.1.3
1st Floor Circulation (Members) 134,
Reduce the length of the dead-end corridor.
----------------------------
Tuesday, August 6, 2024 DF: RTC: The Door 134A is a double egress door. The plan on G1.01 has been revised with symbols to better clarify the door 134A as a means of egressing the space "1st Floor Circulation (Members) 134". [Left of center on Sheet.]
|
8/8/2024
| dfeagle |
|
21) Sheet A9.10 calls out doors 100, 121A, 121B, 125B, Child 130A (with remote lock and PT 302 to have card Readers or Card Readers/Electric Strike.
a) Will there be any special locking arrangements such as Access-Control, Mag-Locks, Door Hardware Release of Electrically Locked Egress Door Assemblies, Delayed-Egress of Electrical Locking Systems, Sensor-Release of Electrical Locking System, etc.? 101:7.2.1.5.6, 7.2.1.6.1.1, 7.2.1.6.2, 7.2.1.6
a) Call out the doors to receive such hardware / systems,
NOTE: I am placing a HOLD 105 Inspection for a revision to review any Access-Control, Special Locking Arrangements.
----------------------------
Tuesday, August 6, 2024 DF: RTC: On Sheets G1.01 [Left and Right] and G1.03 [Right], the doors with special locking arrangements have been tagged with a superscript that correspond to the note on the Door Schedule on Sheet A9.10. The MEANS OF EGRESS LEGEND [at bottom right] of Sheets G1.01, G1.02, etc. have been revised to clarify the meaning of the superscripts. To be clear, no doors will have Delayed-Egress. Pairs of doors with card readers have electric strikes. Doors include; 100 - P.T. ENTRY, 119A - PILATES GROUP, 121A - PILATES PERSONALIZED, 121B - PILATES PERSONALUIZED, 123B - MIND BODY STUDIO, 125A - SPIN, 125B - SPIN, 127A GROUP FITNESS, 130A - CHILDCARE, 302 PHYISCAL THERAPY.
Thursday, August 8, 2024 DF: Reviewer's Response: With the exception of the statement noted above regarding "No Delayed-Egress" and the doors calling out "Electric Strikes" Superscript with "CR, the remaining doors with "CR" and "RL" do not identify the type of Special Locking Arrangement as spelled out in NFPA 1014:7.2.1.5.6 [Door Hardware Release of Electrically Locked Egress Door Assemblies], 101:7.2.1.6.2 [Sensor-Release of Electrical Locking Systems].
The HOLD 105 Inspection will remain for the revision to plans to address the special locking arrangements.
|
| |
|
22) Door Schedule on Sheet A9.10 does not show the Accordion WonDoor in its schedule.
Provide the information in the door schedule for the WonDoor.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Sheet A9.10 has been revised to indicate which doors are wonDoors in the "COMMENTS" column [the 18th column from the Left]. There are six instances: 170, 171, 302G, 313B, 313C, and 313D. Sheet A9.13 has been added the drawing set to include the manufacturer's specification sheets as part of the permit re-submittal.
Thursday, August 8, 2024 DF: Reviewer's Response: A HOLD 105 Inspection for a revision for the installation of the WonDoor is being placed on this permit. The specialized operation and egress requirements will require a more in-depth review of the WonDoor and it's installation.
|
8/9/2024
| dfeagle |
|
23) 3rd Floor Gym (Cardio) towards 1st “WonDoor” looks like it will create a “Dead-end” corridor when the WonDoor is activated. 101:12.2.5.1.3
a) Demonstrate how the WonDoor will not create a Dead-end Corridor.
b) Provide the manufacturer’s specification sheets for the WonDoor.
NOTE: I am placing a HOLD 105 Inspection for a revision to review the WonDoor submittal and its connection with the Fire Alarm System.
----------------------------
Tuesday, August 6, 2024 DF: RTC: The WonDoor product utilizes a code-compliant, accessible push-to-open button door opener to re-open a portion of the accordion door in order for occupants to egress at the will of the occupant before automatically reclosing, functionally similar to the hold-open doors. Sheet A9.13 has been added the drawing set to include the manufacturer's specification sheets as part of permit re-submittal.
Thursday, August 8, 2024 DF: Reviewer's Response: A HOLD 105 Inspection for a revision for the installation of the WonDoor is being placed on this permit. The specialized operation and egress requirements will require a more in-depth review of the WonDoor and it's installation.
|
8/9/2024
| dfeagle |
|
24) Total Travel distance shown for the Enclosed Parking Garage - parking level #1 from parking space by Storage / Maintenance Room 148 to Stair #1 and to Stair #2 is greater than 200’. 101:42.8.2.6.1 Table 42.8.2.6.1
Demonstrate compliance with the maximum travel distance per 101:42.8.2.6.1
NOTE: The distance shown for travel to Stair #1 does not end at the stairway entrance door, as the stairway does not discharge at the exterior of the building. Stairway #1 discharges into the Open-Air Paseo & Arcade corridor and travels approximately another 76 feet to the exterior of the building (exit discharge).
----------------------------
Tuesday, August 6, 2024 DF: RTC: Exit Stair 3 and Exit Stair 4 have been redesigned to serve as Exits for Level 1 parking. On Sheet G1.01 has been updated and clouded [throughout plan] with dimensional lines and notes demonstrating travel to Exits to be within 200'. The redesign of Exit Stair 3 allows access from the parking garage to grade, depicted in Stair Section A13 on Sheet A7.03 [Lower Sheet].
|
8/9/2024
| dfeagle |
|
25) Stairway #1 (Rated 2 hours) does not exit to the exterior (out of the building). The Stairway exits into the open-air Paseo & Arcade corridor/egress space. Egress travel from Stairway #1, 1st floor door to the exterior of the building is approximately 74’.
If you intend to use Stairway #1 as an exit, how will you provide continued egress protection of the Stairway to the exterior of the building?
----------------------------
Tuesday, August 6, 2024 DF: RTC: Response to Comments 25 & 32: NFPA 101:7.7.2 permits 50% of the required exits to discharge through areas on the level of discharge. Additionally, the 2-hour fire barrier separation is continuous to the Ground Level, including a WonDoor separating the Pasco from the Parking Garage [Center of Sheet G1.01], and therefore, Stair #1 is permitted to discharge internally (NFPA 101:7.2.4.3.3).
Thursday, August 8, 2024 DF: Reviewer's Response: Exit Signage is to be installed in Stair 1’s Exit Discharge through the Paseo & Arcade area directing to the exterior of the building [101:7.7.2(3)].
|
| |
|
26) There are stairs that travel from the Egress Exits of the building from Level 1 to the lower ground below. I do not see handrails (and Guards if necessary) for these stairs. 101:12.2.2.3, 101:42.2.2.3, 101:42.8.2.2.3, 101:7.2.2
Demonstrate compliance with 101:7.2.2
----------------------------
Tuesday, August 6, 2024 DF: RTC: Sheet G1.01 has been revised to include additional site context graphically [Throughout]. To clarify, all exits and exit stairs except for Exit #15 and Stair 2 exit to grade. Exit #15 and Stair 2 have a ramp which brings occupants down to grade. G1.01 [Center right of plan] has been revised to show the railing for the ramp. To clarify, Stair 3 has been revised so that the door leads out to grade.
|
8/9/2024
| dfeagle |
|
27) Plans call for Horizontal Exits. There are several noted on the plans. Please identify each Horizontal Exit separately, such as; Horizontal Exit #1, Horizontal Exit #2, etc.
----------------------------
Tuesday, August 6, 2024 DF: RTC: G1.03 has been revised to differentiate between the Horizontal Exits numerically (i.e. Horizontal Exit #2, etc.). [Throughout]
|
8/9/2024
| dfeagle |
|
28) Sheet G10.03 calls out a Horizontal Exit Refuge Area. 101:7.2.4
Compartment A has an occupant load of 1,116 and an egress capacity shown of 883 occupants: Stair #1 (200), Stair #2 (165) Stair #4 (165), Stair #5 (153) and Grand Stair (200). Balance of Compartment A to Horizontal Exit B: 398 occupants.
Compartment B Has an occupant load of 316 and an egress capacity of shown of 165 occupants: Stair #3 (165).
Compartment A is shown with Stairs 1, 2, 4, 5 on its side of the Fire Barrier and Compartment B is shown with only Stair #3 on its side of the Fire Barrier. The Horizontal Exits only indicate a Horizontal Exit from Compartment A to Compartment B. 101:12.2.4, 101:7.4, 42.8.2.4,
a) I only see one exit (Stair #3) for Compartment B, how will you meet the minimum of two (2) exits?
b) Remember to demonstrate remoteness of the exits.
c) Verify common path; 20’ any number of occupants, 75’ for not more than 50 occupants and max travel distances of 200’ on Compartment A side (GYM - Open Plan)
Keep in mind that the Grand Stair is currently under question regarding its ability to be utilized as an Exit Access as noted above. The numbers of occupants in both Compartments A and B may change causing egress capacity issues for both compartments.
----------------------------
Tuesday, August 6, 2024 DF: RTC:
a) The line which delineates Compartment A and B on G1.03 (now magenta) has been revised to clarify the Exit Stair #2 serves Compartment B [Center Right of Sheet]. Both Compartments A and B have access to Exit Stair #1. The Design has been revised to also allow Exit Stair #4 to serve Compartments A and B, Complying with maximum travel distances [Upper Left of Sheet].
b) G1.03 has been revised with additional dimensional symbols to demonstrate remoteness of the exits. [Throughout Sheet]
c) Compliance with common path and maximum travel distance constraints have been verified. Since the parking garage has now been completely separated from the rest of the building with 2-hour fire barrier, the max travel distance for Compartment A would be 250 feet, which is the most restrictive of the nonseparated occupancies (Assembly, Business, Mercantile).
|
8/9/2024
| dfeagle |
|
29) Risk Analysis for Mass Notification System. 101:12.3.4.5
Provide a Risk Analysis for Mass Notification for the building.
----------------------------
Tuesday, August 6, 2024 DF: RTC: The building has low risk of being impacted by the type of potential events outlined in NFPA 72:24.3.11.9 including geological events, biological events, accidental events, intentional events, or technological-caused events.
Tuesday, August 6, 2024 DF: Reviewer's Response: The Risk Analysis is to be a separate document from the Response to Comments [NFPA 101:9.14.3. The Risk Analysis Report is to be provided by the Registered Design Professional (RDP) on letterhead including information noted in 101:9.14.3.1 and provided with a wet seal and wet signature.
|
| |
|
30) Common Paths exceeding 20’ of travel for all occupant loads except for those with 50 or less occupants, which is 75’ of travel (101:12.2.5.1.2):
Level #1: Pilates Personalized 121, Mind-Body Studio 123, Tennis Shop 109, Gourmet Shop (from Tennis Shop to front of restaurant), Storage / Maintenance (Garage).
Level #4: (Mechanical Penthouse on left of Stair #1.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Additional symbols have been made on G1.01 and G1.04 Sheets to clarify the following:
1. Pilates Personalized 121 - Door 121B provides an exit on the opposite side of the room of the exterior egress doors. Door 121B leads out to the "Mind Body Sanctuary" which functions as a pre-function for the Mind-Body Studio 123 and Pilates Group 119. [Left of Sheet G1.01]
2. Mind-Body Studio 123 - Door 123A provides an exit on the opposite side of the room of the exterior egress doors. Door 123A leads out to the "Mind Body Sanctuary" which functions as a pre-function for Pilates Personalized 121 and Pilates Group 119 [Left of Sheet G1.01]
3. Tennis Shop 109 - Doors 102G and 109B provide exits from opposite sides of the space. [Left of Sheet G1.01]
4. Gourmet Shop (from Tennis Shop to Front of restaurant) - Door 105D provides a means of egress from the Gourmet Shop through the Tennis Shop. [Left of Sheet G1.01]
5. Storage / Maintenance (Garage) - Door 148A has been added to the space opposite to Door 148. [Right of Center of Sheet G1.01]
6. Mechanical Penthouse 400. Refer to G1.04 [Left], A1.04 [Left}, and A2.04C [Upper Right].
Thursday, August 8, 2024 DF: Reviewer's Response: Common path of travel has been addressed. However, Pilates Personalized 121 and Mind Body Sanctuary 129 have been affected adversely by the changes and are being addressed by previous comments #18 and #19. I am closing comment pending #18 and #19 compliance.
|
8/9/2024
| dfeagle |
|
31) Max travel distance exceeds 200’ (101:42.8.2.6.1):
Level #1: 1st Floor Garage…
Level 3: GYM (Open Plan) Outdoor Terrace (248’), Pool Storage by Men’s Lockers, Whirlpool to Horizontal Exit (244’), Whirlpool to Grand Stair (224’) (not an approved exit), Parking Garage: Horizontal Exit by Pool Supplies (291’), etc.
Level 4: Mechanical Penthouse on Left of Stair #1 (244’ plus travel down and to exit discharge), Mechanical Penthouse on right of Stair #1 (more than 200’ to Stair #1 and down to exit discharge. Most of the far areas of the parking areas.
----------------------------
Tuesday, August 6, 2024 DF: RTC: A complete 2-hour fire barrier separation will be provided between the Garage and the rest of the building on all levels. The design approach is separated mixed use and will comply with the most restrictive requirements for the occupancy therein.
The design is being reconfigured to comply with the 200 feet travel distance in the enclosed parking garage portion on levels 1, 2, and 3. Level 4 meets the definition of an open parking garage since it is completely open on all four side and to the sky. The natural ventilation of smoke does not inhibit occupants from egressing on this level, therefore, the code allows 400 feet of travel distance.
Drawing Sheets impacted: G1.01, G1.02, G1.03, and G1.04 [center of plans and throughout], as well as respective A1.0# and 2.0# Sheets. Walls between Parking Garage and the rest of the building are clarified to have 2-hour fire rating and doors to have 90-minute fire rating, typically.
|
8/9/2024
| dfeagle |
|
32) Horizontal Exit Fire Barriers. I do not see where the 2-hour Fire Barriers continues to ground level. 101:7.2.4.3.1, 101:7.2.4.3.3
----------------------------
Tuesday, August 6, 2024 DF: RTC: Response to Comments 25 & 32: NFPA 101:7.7.2 permits 50% of the requires exits to discharge through areas on the level of discharge. Additionally, the 2-hour fire barrier separation is continuous to the Ground Level, including a WonDoor separating the Pasco from the Parking Garage [Center of Sheet G1.01], and therefore, Stair #1 is permitted to discharge internally (NFPA 101:7.2.4.3.3).
Drawing Sheets impacted: G1.01, G1.02, G1.03, and G1.04 [Center of plans and throughout], as well as respective A1..0# and A2.0# Sheets. Walls between Parking Garage and rest of the building are clarified to have a 2-hour fire rating and doors to have 90-minute fire rating, typically.
|
8/9/2024
| dfeagle |
|
33) Horizontal Exit Fire Barrier utilizes “Fire Sprinkler Water Curtain” protected glass in a 2 Hour Fire Barrier; Horizontal Exit Fire Barrier and Grand Stair enclosure, partial Enclosure(?). The plans include doors in the 2-hour Fire Rated Barrier.
Point out / Demonstrate compliance with NFPA 13:8.15.26
----------------------------
Tuesday, August 6, 2024 DF: RTC: General note 5 added to FP1.01 demonstrating FP compliance with NFPA 13.8.15.26. Note added near Col F.9 and 13 on FP1.01 and FP1.03 identifying location of the fire sprinkler curtain wall.
Thursday, August 8, 2024 DF: Reviewer's Response: Understanding that NFPA 13 is the Standard for the Installation of Sprinkler Systems [how to install them]. And, that that the Florida Fire Prevention Code [FFPC], which contains NFPA 1 and NFPA 101, is the Prescriptive and Governing Code.
Further Review of NFPA 101 Chapters; 8 [Features of Fire Protection], 12 [New Assembly], 36 [New Mercantile], 38 [New Business] and, Chapter 42 [Storage], I am not able to find where the use of Fire Sprinklers are permitted to be used as part of a Fire Barrier, Fire Wall, or other fire separation with the exception of specific use in Atriums [101:8.6.7(c)].
If you are looking to use a Life Safety Design such as the "Fire Sprinkler Water Curtain" not provided for in the Prescriptive Code [101:4.4.2], You will need to provide a Complete and Comprehensive documentation by a Fire Protection Engineer demonstrating compliance with 101:4.4.3 and Chanter 5 [Performance Based Option] of NFPA 101. [101:5.1.3]
|
| |
|
34) Plans indicate Childcare areas with outdoor Nursery Playground.
a) Will this Childcare Facility be licensed by Florida Department of Children and Families (DCF) or other County, State or another agency? If NO,
b) Will the child’s relative or guardian be within the same building the whole time the child is in the Childcare Facility (101:16.1.1.7)? If NO,
If the answer to “a)” is YES, and/or the answer to “b)” is NO, then the childcare occupancy will be reviewed as a daycare under chapter 16 of NFPA 101. Otherwise,
The childcare areas will be reviewed as Assembly. 101:12.1.2, 6.1.2.1
----------------------------
Tuesday, August 6, 2024 DF: RTC: a) NO, the Childcare areas with outdoor Nursery Playground are not intended to be licensed by DCF or other entity. B) Yes, the child's relative or guardian is intended to be within the same building the whole time the child is in the Childcare Facility.
|
8/9/2024
| dfeagle |
|
35) Fire Pump Room does not appear to be Fire Separated from the remainder of the building. NFPA 20:4.13.1.1.2
Provide Fire Separation of the Fire Pump Room and the remainder of the building (walls/ceiling/floor).
----------------------------
Tuesday, August 6, 2024 DF: RTC: Walls separating the Fire Pump Room from the remainder of the building have been revised, tagged, and clouded as a 2-hour fire rated assembly that spans up to the bottom of the floor slab above, which shall also have a 2-hour fire rating. The floor is simply the slab-on-grade, with other spaces of the building below. Revised on Sheets G1.01 [Upper Left], A1.01 [Upper Left], A2.01C [Left of Center].
Fire Dampers added to Fire Pump 151 penetrations on Sheet M2.01D.
|
8/9/2024
| dfeagle |
|
36) Fire Pump Room: I do not see any Emergency Lighting (EL) in the Fire Pump Room. The EL in the Fire Pump Room is to be 3.0 ft-candles at the floor AND Shall maintain the lighting level of 3.0 ft-candles for a minimum of 2 hours. NFPA 20:4.13.5
Provide the above Emergency Lighting in the Fire Pump Room.
NOTE: The EL levels and run time are not the same as the standard EL illumination required by 101:7.9.2.1.1. The EL required in the Fire Pump Room is required throughout the room. Provide documentation (spec sheets) the EL meets these requirements.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Sheets E0.01 and E3.01B updated to include fixture type 'LAE2' in Fire Pump Room. Specification Sheets attached (page 6/9).
|
8/9/2024
| dfeagle |
|
37) Emergency Lighting (EL) is not shown in some of the Rooms and areas:
Level 1: Throughout the exterior “Level Exit” (see Sheet G1.01) areas, Outside Dining by the Gourmet Shop and the exterior seating (means of egress) areas between them. 101:12.2.9. Also, No EL shown in Stairs 1, 2, 3, 4 and 5, Large Storage Room 147B, Storage/Maintenance 149, Need in gourmet Shop behind counter area, Kitchen Men’s Restroom 115 in the back, Women’s Restroom 116, Men’s Restroom 117, Mind-Body Sanctuary 118, Group Waiting 129, MDF Room, Trash Holding 150.
Level 2:
Level 3: I do not see any EL’s in the outer spaces/outcrops of the GYM (OPEN PLAN parallel with the Open Terrace (including the Open Terrace), Physical Therapy rooms including the PT storage Room, Open Terrace by Living Room, Pool Storage by Horizontal Exit, Soiled Terry Holding, Under/in the area of the exterior pool deck (trellis area), along the glass wall of the pool area (poolside of glass) to the Pool Storage Room Men’s and women’s Locker Rooms, Shower Area closest to elevator, Men’s and women’s Spa areas.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Throughout the exterior "Level Exit" (see Sheet G1.01) Areas: Type 'Y' fixture provided over all exterior egress exits:
* Outside Dining by the Gourmet Shop and the exterior seating (means of egress) areas between them: Type 'Y' fixtures added to this area to work in conjunction with type 'LD2E' to satisfy this requirement. Refer to Sheet E3.01B
* Stairs 1, 2, 3, 4 and 5: Type 'A' in the stairwells is specified with integral battery refer to E0.01. Type 'Y' fixture provided at exterior exits refer to Sheets E3.01A/B.
* Large Storage Room 147B, Storage/Maintenance 149: Type 'LAE' added to these areas for compliance, refer to Sheet E3.01A.
* Need in Gourmet Shop behind counter area: Four (4) type 'LD1E' added to this area for compliance, refer to Sheet E3.01B.
* Kitchen: Kitchen provided with type 'BE', refer to Sheet E3.01B.
* Men's Restroom 115 in the back: Type 'LD1E' added to this area for compliance, refer to Sheet E3.01B
* Women's Restroom 116: Type 'LD1E' added to this area for compliance, refer to Sheet E3.01B
* Men's Restroom 117: Type 'LD1E' added to this area for compliance, refer to Sheet E3.01B
* Mind-Body Sanctuary 118: two (2) type 'LF2E' added to this area for compliance, refer to Sheet E3.01B.
* Group Waiting 129: Three (3) type 'LD1E' added to this area for compliance, refer to Sheet E3.01B.
* MDF Room: type 'LAE' added to this area for compliance, refer to Sheet E3.01B.
* Trash Holding 150: two (2) type 'LAE' added to this area for compliance, refer to Sheet E3.01A/B.
Thursday, August 8, 2024 DF: Reviewer's Response: Review of the updated Emergency Lighting (EL) Sheets revealed the need for additional EL's in the following areas:
Sheet E3.01A: Open Air Arcade area.
Sheet E3.01B: Childcare 130: In the area of the rear exterior exit and in the smaller room with door 130B.
Sheet E303A: Recovery Area 314, Outdoor Terrace 304, Workout Area by outdoor Terrace 304's exit door 304, PT Ar3ea [Lower Right], Breakroom 307A.
Sheet E303B: Pool Deck (around the pool), exterior corridor from poll area to an(and past) Circulation [West Area Exit Door 326].
Sheet E3.04A & E3.04B: No EL's are shown in Mechanical Rooms 400 & 401.
|
| |
|
38) Gourmet Shop and Kitchen: It appears there may be a CO2 system. Will the CO2 beverage system exceed 100 pounds? If so, demonstrate compliance with NFPA 55:13.10.
NOTE: Make sure to include CO2 tank location, CO2 piping to mixing location (ex- bag/box), indicate which option will be used (ventilation vs sensor/notification) AND show compliance with chosen option of compliance. If Sensor/notification, show locations of the devices.
NOTE: The Co2 system and its detection/notification system can be a deferred submittal if you desire. Please note this on the plans if you plan on submitting as a deferred submittal.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Keynote added to M4.01 to specify the CO2 system and detection/notification system by others and will be deferred submittal.
Tuesday, August 6, 2024 DF: Reviewer's Response: A HOLD 105 (framing) inspection is being placed on this permit for a deferred submittal for the CO2 detection / notification system.
|
8/9/2024
| dfeagle |
|
39) Gourmet Shop and Kitchen: I do not see where cooking oil (new and/or used) will be stored. If inside the building, show compliance with 1:66.19.7. If outside the building, indicate tank size (in gallons) and be prepared to submit for tank permit if over 60 gallons. Permit will need to show compliance with NFPA 1 Chapter 66 (1:66.9.19, 1:66.21 and 1:66.222) for a combustible IIIB liquid.
NOTE: The Oil storage tanks and/or oil storage system can be a deferred submittal if you desire. Please note on the plans if you plan on submitting as a deferred submittal.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Oil storage tanks and/or oil storage system is intended to be a deferred submittal. This intention is included on G1.01 plan as a note near the Kitchen.
Tuesday, August 6, 2024 DF: Reviewer's Response: A HOLD 105 (framing) inspection is being placed on this permit for a deferred submittal for the oils storage tank(s) and/or oil storage system.
|
8/9/2024
| dfeagle |
|
40) Lighting Plans Marked by Sheet Numbers LDxx have “FOR REFERENCE ONLY” printed on them. These will not be used for review. If they are intended to be used in the review process remove the “FOR REFERENCE ONLY” statement.
----------------------------
Tuesday, August 6, 2024 DF: RTC: The Lighting Plans in question have been removed.
|
8/13/2024
| dfeagle |
|
41) Horizontal Exit Refuge Area: Plans call for a Horizontal Exit Refuge Area on Level 3 in the Parking Garage. There is an area marked out on the parking deck that covers several parking spaces. Furthermore, Code Summary 4.7 on Sheet G0.03 identifies the floor as an Area of Refuge and the elevators will have two-way communication per FFPC §7.2.12.1.1. The reference “FFPC §7.2.12.1.1” or, 101:7.2.12.1.1 references the two-way communication on the elevator “landing”, not in the elevator or the elevators inside required emergency communication requirement. Please note that the elevators are NOT in Compartment “B” (Refuge Area) but are located in Compartment “A”.
a) Demonstrate compliance with 101:7.2.12.1.1(1), (2) and (3),
b) Point out the locations of the two-way communication stations,
c) Provide samples of the two-way communication instructions
d) How will you provide a two-way communication station in Compartment “B” since there are no elevators/elevator landings in Compartment B?
----------------------------
Tuesday, August 6, 2024 DF: RTC: On Sheet G1.03, the hatched area labeled "HORIZONTAL EXIT REFUGE AREA" is intended to provide a graphic reference for the minimum refuge area required by code, relative to the larger overall area that Compartment B provides. to clean up the graphic, the hatched area has been revised to not conflict with parking spaces.
Sheets G1.02, G1.03 and G1.04 have been revised and clouded to note the location of two-way communication stations outside of each elevator at Levels 2, 3 and 4. The corresponding text note refers to additional information added on sheet A7.11 at the bottom left of the Sheet., which outlines the 101:7.2.12.1 code requirements and provides samples of the two-way communication instructions. [Throughout Sheet, near elevator locations]
The pair of elevators nd landings adjacent to STAIR 1 are intended to be a part of Compartment B. The thick magenta dashed line which delineates the Compartments on Sheet G0.03 [Throughout plan] has been corrected. The two-way communication station is located between the two elevator doors with compliant clear floor space. G103 has been revised to note and illustrate the location.
|
8/13/2024
| dfeagle |
|
42) Carbon Monoxide Detection: I am unable to locate carbon monoxide detection and warning equipment:
a) On the ceiling of rooms that contain permanently installed fuel-burning appliances. 101:12.3.4.4(1)
b) Centrally located within occupiable spaces served by the first supply air register from permanently installed fuel-burning HVAC systems. 101:12.3.4.4(2)
c) Centrally located within occupiable spaces adjacent to an attached garage. 101:12.3.4.4.1(3)
Point out / provide CO detectors.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Carbon Monoxide Detection provided in the following locations:
* In Pool Equip. 144 on M2.01A with Keynote 7.
* Between Col G.6 and H on 2/M4.01 with Keynote 8.
Per 101:12.3.4.4.2, carbon monoxide detectors are not required in occupiable spaces with attached garages that are open parking structures (locations where Level 3 of the building open to the top level of the parking deck) or mechanically ventilated structures in accordance with the mechanical code (locations where level 1 of the building opens to the parking deck).
|
8/13/2024
| dfeagle |
|
43) I am unable to locate elevator information. 101:30.5.3, 69A-47
Please point out where it shows:
- The new elevator complies with ASME A17.1/CSA B44. 101:9.4.2.1,
- The new elevator complies with Fire Fighter recall. 101:9.4.3.1
- If the elevator is operated by solid state equipment, show where compliance with 101:9.4.5 is illustrated.
- The elevator is fitted with the “Emergency Response Region #3” Key. (NFPA 1:11.3.6, FAC 69A-47.012/69A-47.015) This key will allow the override and operation of the elevator.
----------------------------
Tuesday, August 6, 2024 DF: RTC: General Notes at the top-left corner of Sheets A7.01, A7.02, A7.03, A7.04, and A7.05 have been revised to clarify the necessary compliance with the codes and standards outlined in this Comment 43.
|
8/13/2024
| dfeagle |
|
44) Food Service Equipment Sheets include Sheets containing information about the Type 1 Hood and its Suppression system. The Hood and Suppression System is to be deferred Submittal.
a) Remove all Hood and Suppression Information from these plans, OR
b) Place “Fore Informational Purposes Only” or “Deferred Submittal” on the Sheets.
----------------------------
Tuesday, August 6, 2024 DF: RTC: The Sheets in question have been removed.
|
8/13/2024
| dfeagle |
|
45) Sheet IA0.01 provides the Interior Finish Requirements and the Wall & Ceiling Finish Schedules based on the table as defined in the IBC Section 803.1 and 803.5.
Provide the wall, ceiling and floor finish schedule as noted in NFPA 101:12.3.3
----------------------------
Tuesday, August 6, 2024 DF: RTC: The Interior Designer's (TJS) Finish Specification has been included in the resubmittal. It demonstrates compliance with NFPA 101:12.3.3.
|
8/13/2024
| dfeagle |
|
46) Finish Schedule on Sheet IA9.11 states “Refer to TJS FFE Specifications for Details” in the NOTES portion of the Schedule for all items. I am not able to locate the “TJS FFE”.
Please point out the location of the “TJS FFE” or provide the TJS FFE for review.
----------------------------
Tuesday, August 6, 2024 DF: RTC: Sheet IA9.11 has been revised to correct the note to say instead "REFER TO TJS FINISH SPECIFICATIONS FOR DETAILS." Aforementioned in Response to Comment 45, the TJS Finish Specification has been included in this resubmittal.
|
8/13/2024
| dfeagle |
|
47) As noted in Code Summary 10.5 (panic hardware requirement) on Sheet G0.03, and as this is a Mixed Occupancy, once the occupant loads have been updated verify and make changes in the plans regarding the Panic Hardware requirement.
----------------------------
Tuesday, August 6, 2024 DF: RTC: The Door Schedule on A9.10 has been revised to reflect the updated occupant loads. The column on the schedule that indicates panic hardware is 10th from the right. Revisions since initial submittal have been clouded.
Thursday, August 8, 2024 DF: Reviewer's Response: After reviewing the resubmittal the following doors are in the means of egress and require panic hardware: 191 [Stair 1], 102G [Tennis Shop].
|
| |
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Occupancy Sensors NFPA 101: 7.8.1.2.2 Unless prohibited by Chapters 11 through 43, automatic lighting control devices shall be permitted to temporarily turn off the illumination within the means of egress, provided that each lighting control device complies with all of the following: (1) In new installations, the lighting control device is listed. (2) The lighting control device is equipped to automatically energize the controlled lights upon loss of normal power and is evaluated for this purpose. (3) Illumination timers are provided and are set for a minimum 15-minute duration. (4) The lighting control device is activated by any occupant movement in the area served by the lighting units. (5) In new installations, the lighting control device is activated by activation of the building fire alarm system, if provided. (6) The lighting control device does not turn off any lights relied upon for activation of photoluminescent exit signs or path markers. (7) The lighting control device does not turn off any battery-equipped emergency luminaires, unit equipment, or exit signs.
Be Prepared to Show Compliance at the time of your Fire Alarm Final or Fire Final.
|
8/7/2024
| dfeagle |
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: 101:8.3.2.4 Each new Fire Wall, Fire Barrier, Fire Partition, Smoke Barrier, Smoke Partition, or any other new wall required to have protected openings shall be permanently identified with signs or stenciling above any decorative ceiling and in concealed spaces, with the wording “FIRE AND SMOKE BARRIER – PROTECT ALL OPENINGS”, or similar language. Such signs or stenciling shall be 4 in. high letters, ½ in. stroke, and not more than 15 ft. on center.
|
8/7/2024
| dfeagle |
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following: NFPA 101 7.9.2.3 (1) Failure of a public utility or other outside electrical power supply (2) Opening of a circuit breaker or fuse (3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities. NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2.
|
8/7/2024
| dfeagle |
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Air handlers with more than 2000 CFM are required to have duct smoke detectors. NOTE: If there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. (NFPA 90A:6.4.4.2) Where smoke detectors required by 6.4 are installed in a building not equipped with an approved fire alarm system as specified by 6.4.4.2, the following shall occur: 1. Smoke detector activation required by section 6.4 shall cause a visual signal and an audible signal at a normally occupied area. 2. Detector troubles shall be indicated visually or audibly in a normally occupied area identified as air duct
|
8/7/2024
| dfeagle |
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Buildings containing Fire Alarm Systems, Fire Sprinkler Systems, etc. and/or Security Systems that make it difficult to access the building in an emergency are required to have a Fail-Safe box. NFPA 1:18.2.2.1
Please contact St Johns County Fire Rescue Secretary Dawn Lyons at 904-209-1712 for the correct order form.
|
8/7/2024
| dfeagle |
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- Interior wall and ceiling finish materials shall be Class A or Class B in all corridors and lobbies and shall be Class A in enclosed stairways. 101:12.3.3.2
- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:12.3.3.5.
- Interior floor finish in exit enclosures and exit access corridors and in spaces not separated from them by walls complying with 12.3.6 shall be not less than Class II.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.
|
8/7/2024
| dfeagle |
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- Fire alarm system (Voice Evac) (E0.00) - Fire sprinkler system (Supervised) - Fire underground - Kitchen hood (Water Wash / R-102 Suppression) - Kitchen suppression system - Fire/smoke damper inspections - HOLD 105 INSP for Revision: Fire Rated WonDoor Installation - HOLD 109 INSP for Revision: Special Locking Arrangements - HOLD 105 INSP for CO2 Detection/Notification System [RTC#38, M4.01] - HOLD 105 INSP for Cooking Oil Storage Tank and/or Oil Storage System [RTC #39] - HOLD 105 INSP for BDA Test/Evaluation and/or Permit [T0.02, T9.08, T9.09] - HOLD 109 INSP for MIC Evaluation by Sprinkler Contractor – FP1.01: 61G15-32.004(h) - HOLD 109 INSP for Standpipe System - - -
|
| |
|
48) Tuesday, August 6, 2024 DF: New comment based on 1st Resubmittal Review: 61G15-32.004(f) provides information for a Flow Test that is dated 01/31/2023. This test date is more than one (1) year old. The test is to be conducted within one (1) year prior to the date of the EOR's signed and sealed document.
Provide an updated EOR's 61G-15-32.004 with an updated Flow Test within one (1) year.
|
| |
|
49) Thursday, August 8, 2024 DF: New comment based on review of 1st Resubmittal: I am not able to find a "Door Hardware Schedule for ALL of the Doors. The Project Manual [087100] does not provide information on the Hardware Sets and/or Hardware to Door Schedule. The Door Schedule on Sheet A9.10 States "SEE IA" in the Hardware Set column for each door. Sheet AI9.10 provides a Door Schedule that does not address ALL doors throughout the building/garage. The Hardware Sets identified [IA Hardware Column] (i.e. "HD-101") are found on Sheet IA9.11 in the Decorative Hardware Schedule which does not provide information on door closers, fire rated-hardware, hold-open devices, flush-bolts automatic or manual, etc.
Provide a Complete Door and Hardware Set Schedule for AL:L the doors and update any Door Schedule, Door and Hardware Schedule, Door Hardware Schedule in the Plan Set to match.
|
| |
|
50) Thursday, August 8, 2024 DF: New comment based on review of 1st Resubmittal: I am not able to determine if the Normal Egress Lighting in the Stairways meet the 10 ft-candle along the walking surface as required by 101:7.8.1.3(1). Also, I am not abler to determine if the Emergency Lighting on all 4 levels of the Parking Garage provide 1 ft-candle along the walking surface as required by 101:7.9.2.1.1.
a) Provide Normal Egress Photometrics demonstrating compliance with 101:7.8.1.3(1) in ALL stairways AND,
b) Provide Emergency Lighting Photometrics demonstrating compliance with 101:7.9.2.1.1 on ALL 4 levels of the Parking Garage.
|
| |
|
51) Thursday, August 8, 2024 DF: New comment based on review of 1st Resubmittal: Doors 102D, 102E, and 103C in the 2 hour wall separating the Parking Garage and LOGO Shop 103 and Retail 102 are not identified as being fire rated in the Door and Hardware Schedule on Sheet A9.10. 101:8.3.3.2.5
Update the Door and Hardware Schedule to reflect the doors as fire rated as well as their hardware.
|
| |
|
52) Thursday, August 8, 2024 DF: New comment based on review of 1st Resubmittal: Door 337B [by Stair 5] opens and blocks Door 395's opening into Stair 5.
Change door #337B position / location so the door swing does not block Stair 5's opening/access.
|
| |
|
53) Thursday, August 8, 2024 DF: New comment based on review of 1st Resubmittal: There are several large storage rooms throughout the building. The following are some of the Storage Rooms Noted. Rooms 182A [A2.01A], Trash Holding 150 [A2.01B], Storage/Maintenance 148 [A2.01B], BOH 111 [A2.01C], Storage 131B [A2.01C], Pool Storage 131B [A2.03C], Pool Storage 342 {A2.03C], Soiled Terry Holding 343 [A2.03C], Pool Equipment [144]. 101:12.3.2.1.2.
Provide protection in accordance with Chapter 8.7 of NFPA 101.
NOTE: If you elect to use the Sprinkler option in lieu of the Fire Barrier option you will need to provide a Smoke Partitions in accordance with 101:8.7.1.2. Provide Sheets showing the Smoke Partitions locations and any associated smoke dampers.
|
| |
|
|