SJC Home
Clearance Sheet C2024-003701

 Department IssuesSigned OffIntl

Plan reviewed for Revision to approved plans addressing Revisions 2 (11/11/2024) and 3 (01/17/2025). NOTE: Adding a Full Kitchen.

Sheets provided for review: G001, G003, A100, A201, A201a, A231a, A241a, A251, A301, A302, A500, A510, A521, A354, A810, A811, A901, A904, A905, A910, A911, M001, M002, M003, M201, M203, P001, P002, P201, P203, P301, P401, P501, FP201, E000, E001, E003, E100, E201, E301, E401, E402, FP001.

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

2/25/2025 dfeagle

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

2/25/2025 dfeagle

1) Plans indicate a "NEW" Kitchen including cooking equipment and a Type I Grease Hood have been added to the plans. The Hood, Ductwork, Hood Suppression System is required to be separately from the revision as a deferred submittal.

A HOLD 105 Inspection has been placed on this permit for the submittals of the Hood and Suppression systems.

2/25/2025 dfeagle

2) Revision Plans include a Non-Signed, Non-Sealed FP201 Sheet imbedded inside the plan Set. There is also a separate Sheet FP001 and FP201 that are Wet Sealed and Wet Signed included (loose) with the plans. The signed and sealed FPO Sheets will be approved and the NON-signed and NON-sealed FP sheet 201 will be marked as "NOT PART OF THIS PERMIT".

2/25/2025 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating they evaluated that the existing system meets the occupancies Code requirements and no work to be done to the existing system to meet Code based on the work in this permit:

- Fire Alarm System - Sheet E401, ALSO; Hood Suppression Connection (M002)
- Kitchen Hood - Revision Sheet M002
- Kitchen Suppression System
- HOLD 105 INSP - Revision - Main Drive Area of Service Bay: CMMT #18
- HOLD 105 INSP - Revision - Aboveground Storage Tanks - See Review Comment #14
- 
-

2/25/2025 dfeagle