SJC Home
Clearance Sheet C2024-003701

 Department IssuesSigned OffIntl

Plan reviewed for 27,858 SF, Two (2) Story, Type IIB[II(000)] Construction, Ordinary Hazard Contents,  Wet Sprinkler system [NFPA 13] with Remote FDC, Service Center has two HVLS Fans. Fire Alarm System throughout [E401].

Non-Separated Mixed Use: Special Purpose Industrial, Storage, Business.

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

-----------------------------

Thursday, November 21, 2024 DF: Review of 1st Resubmittal. NOTE: ALL NEW Plan Set provided.

11/25/2024 dfeagle

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

11/25/2024 dfeagle

1) The majority of the Sheets have “NOT RELEASED FOR CONSTRUCTION OR PERMIT” in the Sheet’s Title Block. I cannot approve these plans with this statement on the Sheets.

Remove this statement.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Notes. "NOT RELEASED FOR CONSTRUCTION OR PERMIT" has been removed from all Sheets.

11/21/2024 dfeagle

2) Applicable Code Section on Sheet G003 does not call out The Florida Fire Prevention Code 8th Edition [FFPC]. 69A-3.012.

Call out the FFPC in the Applicable Code Section.

-----------------------------

Thursday, November 21, 2024 DF: RTC: "The Florida Fire Prevention Code 8th Edition {FFPC}. 69A-3.012" was called out on the "Applicable Code Section", upper-left section of Sheet G003.

11/21/2024 dfeagle

3) Fire Protection Sheets FP001 and FP201 are not Wet Stamped and Wet Sealed.

Have the FP Sheets Wet Sealed and Wet Signed by the Fire Protection Engineer.

NOTE: The FDC shown on Sheet FP001 {Fire Protection Site Plan] and Sheet FP201 [outside Sprinkler 134 room] is shown on the building. Per the approved Site Plan, the FDC is remote from the building.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Noted. Per the approved Site Plan, the FDC has been moved from outside room Sprinkler 134 to landscaping island north of the service drive. This has been captured on Permit/Bid issued 07.17.2024 and called out on the "FIRE PROTECTION SITE PLAN", lower-right section of Sheet FP001 & "FIRE PROTECTION PLAN-LEVEL-1-PHASE 1", Center-left section of Sheet FP201.

11/21/2024 dfeagle

4) Sheet G003 under Code DATA Analysis (FBC) Moderate-Hazard Storage is called out for the Hazard Class. This classification is not found in Chapter 6.2 of NFPA 101. Provide the classification of hazard of contents per Chapter 6.2 of NFPA 101.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Moderate-Hazard Storage, Group S-1 is a type of occupancy per section 311.2 of FBC, Not NFPA 101. According to the hazardous contents will storage in this facility, the classification of hazard of contents shall be "6.2.2.3 Ordinary Hazard Contents" per Chapter 6.2 of NFPA 101.

11/21/2024 dfeagle

5) There is a discrepancy between the FBC Building square footages and the FFPC square footages; particularly the “Total Level 1 & 2” as shown on Sheet G003.

The square footages for any given room, level and/or building should match between the FBC and the FFPC. Update the Sheet.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Noted. The discrepancy between the FBC and FFPC building SF has been corrected and called out on the "CODE DATA ANALYSIS-FBC" & "CODE DATA ANALYSIS-FFPC", center of Sheet G003.

11/21/2024 dfeagle

6) Provide completed Hazardous Materials Inventory Statement in accord with NFPA 1:60.1.6, (See Section II (Hazardous Materials Inventory Statement) of “Hazardous Materials Management Plan” Annex C.3.1 of NFPA 400 (400:1.12.1), 2019 Edition. If material quantities exceed MAQ be prepared to show compliance with appropriate section of hazardous materials code (NFPA 1 Ch.60).

Tuesday, September 3, 2024 DF: This comment is duplicated in comment #15.

9/3/2024 dfeagle

7) Will there be outside storage of more than 500 tires? If yes, demonstrate compliance with Chapter 33 of NFPA 101.

-----------------------------

Thursday, November 21, 2024 DF: RTC: There will NOT be outside storage of more than 500 tires. The capacity of the "Tire Storage" showing on A102 is significantly less than 500.

11/21/2024 dfeagle

8) Sheet A201a calls out a Café’ 136. Will there be any cooking? If yes, call out any cooking equipment and demonstrate compliance with Chapter 50 of NFPA 1.

-----------------------------

Thursday, November 21, 2024 DF: RTC: There is no cooking equipment in room Café 136 or any other spaces in this building.

11/21/2024 dfeagle

9) There are Three (3) vertical openings; two un-enclosed stairs and a large 18’-8” x 19’ vertical opening in the Parts 114 / Parts 201. Which option (if applicable) of 101:40.3.1 or Section 8.6 of NFPA 101 are you using for protection of these vertical openings?

-----------------------------

Thursday, November 21, 2024 DF: Per discussion with AHJ, the following decisions/changes have been made to these (3) openings. The occupancy classification for parts 114/201 shall be (S) Storage and opening protection should comply with FFPC 42.3.1 instead of 40.3.1. The unenclosed stair near the south exterior wall of parts 114 has been relocated and changed to an exterior egress stairway. There is no longer an unenclosed opening at this location. Door 201, with exit sign and exterior emergency light has also been added for exiting from the second level of Parts to the exterior stair. The other stairs are a convenience stairway which is protected by an automatic sprinkler system, fire alarm system and other fire safety measures and should not require to be enclosed. The large 18'-8" x 19" vertical opening shall be permitted as an unenclosed vertical opening as it complies with all the requirements per FFPC 8.6.9.1. Additionally, the proposed flooring on the 2nd level parts remains as an open steel grating, and classified as an unenclosed vertical opening, meeting the requirements of FFPC 8.6.9.1.

11/25/2024 dfeagle

10) I was not able to find Elevations of the Stairs demonstrating compliance with 101:40.2.2.3 and 101:7.2.2.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Elevations and plans of the exterior egress stairway demonstrating compliance with 101:40.2.2.3 and 101:7.2.2 have been provided on A701. Vendor provided convenience stairs will be submitted separately as part of the mezzanine permit.

11/22/2024 dfeagle

11) Sheet E301 shows two (2) large HVLS fans in the Service Shop132. The installation of HVLS fans in buildings equipped with sprinklers, including ESFR sprinklers, shall comply with the following:
(1) The maximum fan diameter shall be 24 ft (7.3 m).
(2) The HVLS fan shall be centered approximately between four adjacent sprinklers.
(3) The vertical clearance from the HVLS fan to sprinkler deflector shall be a minimum of 3 ft (0.9 m).
(4) All HVLS fans shall be interlocked to shut down immediately upon receiving a water flow signal from the alarm system in accordance with the requirements of NFPA 72.  13:11.1.7

-----------------------------

Thursday, November 21, 2024 DF: RTC: (1) The diameter of the proposed fan will be installed is 12'. Please see the attached spec for the proposed HVLS fan. (2) Noted. Please see added notes and sections for HVLS fan and sprinkler system on FP201. (3) Noted. Noted. Please see added noted and sections for HVLS fan and sprinkler system on FP201. (4) Please see keynote P88 on Sheet E201 and Fire Alarm Riser Diagram on E002 - relays and activation shown, no change needed.

For installation of the HVLS, GC will ensure to follow NFPA 13 compliance in building equipped with sprinklers:

·       Fan must be centered approximately between four adjacent sprinklers

·       Vertical clearance from fan to sprinkler deflector must be a minimum of 3 feet

·       Fan must be interlocked to shut down immediately upon a waterflow alarm from the building’s fire alarm system

·       Interlock with building’s fire alarm system shall be in accordance with requirements of NFPA 72

Proposed HVLS specifications sheets attached for reference.

11/22/2024 dfeagle

12) Door Schedule on Sheet A500 does not identify the hardware sets by numbers or letters as typically found in plans hardware schedules. Project Manual section 08-7110-1 through 08-7110-3 is not centered on the pages correctly and part of the information is hidden in the binding. Also, the information provided that is legible does not clearly identify the type, make model of the hardware and to which specific door the hardware belongs to.

a) Update Sheet A510 Door and Hardware Schedule with a hardware set identification number/letter that is parallel/coordinated with the Projects Door Hardware information, AND

b) Update the Project Manual’s 08-7110 {Hardware Schedule] pages to match Sheet A500’s Door and Hardware Schedule

-----------------------------

Thursday, November 21, 2024 DF: RTC: Project Manual 08-7110-1 through 08-7110-3 is centered on pages. All columns are shown correctly on the printed pages. The "HARDWARE SET" column in D"DOOR SCHEDULE" of Sheet A510 should match "HARDWARE SET" column in Project Manual 08-7110.

11/22/2024 dfeagle

13) Will there be any Special Locking Arrangements including but not limited to: Mag-Locks, Delayed-Egress Electrical Locking Systems [101:7.2.1.6.1], Sensor-Release of Electrical Locking Systems [101:7.2.1.6.1.2], Door Hardware Release of Electrically Locked Egress Door Assemblies, etc.

If yes, call out on plans. These doors will be reviewed as a deferred submittal and a HOLD 105 Inspection will be placed on the plans for this submittal.

-----------------------------

Thursday, November 21, 2024 DF: RTC: There is no Special Locking Arrangements including but not limited to: Mag-Locks, Delayed-Egress Electrical Locking Systems [101:7.2.1.6.1], Sensor-Release of Electrical Locking Systems [101:7.2.1.6.2], Door Hardware Release of Electrically Locked Egress Door Assemblies, etc. Only standard panic hardware is being used on egress doors, both interior and exterior.

11/22/2024 dfeagle

14) Will there be any aboveground or below ground new or used oil storage tanks greater than 60 gallons? If yes, you will need to provide an SJC Fire Marshals Permit and information on the quantity and type of fluid being stored.

-----------------------------

Thursday, November 21, 2024 DF: RTC: As clarified by AHJ, this comment does not apply to this facility.

Thursday, November 21, 2024 DF: Reviewer's Response: The Hazardous Materials Inventory indicates there will be 500 Gallons of 5w30 Oil and 500 Gallons of 5w40 oil stored on the premises. Sheet A251 identifies several 5 large tanks in the COMP/FLUIDS Room 133 but does not identify the capacity of each tank. 

Identify which tanks will have which liquid and it's capacity.

Monday, November 25, 2024 0830 hrs. DF: I spoke with Jiazhen Sun via phone regarding this comment. A HOLD 105 (Framing) Inspection is being placed on this permit for a Revision to provide the Manufacturer's Spec Sheets for the Above Ground Tanks, What each tank will be holding (i.e. 5w40 Motor Oil, etc.).

11/25/2024 dfeagle

15) Provide completed Hazardous Materials Inventory Statement in accord with NFPA 1:60.1.6, (See Section II (Hazardous Materials Inventory Statement) of “Hazardous Materials Management Plan” Annex C.3.1 of NFPA 400 (400:1.12.1), 2019 Edition. If material quantities exceed MAQ be prepared to show compliance with appropriate section of hazardous materials code (NFPA 1 Ch.60).

Guidance: Make sure to include hazard class(es) in accord with NFPA 1, and any sub classes so I am able to check the designers work to make sure chemical's requirements met. Not all chemicals are hazardous and not all hazardous chemicals will have sub classes. Some chemicals can also fall into 1 or more hazard classes. If you need someone to guide your project with chemicals to meet Code you may need to reach out to an Industrial Hygienist.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Noted. Completed Hazardous Materials Inventory Statement has been provided in a separate document for review and reference. No material quantities exceed MAQ will be stored in this facility.

11/25/2024 dfeagle

16) Will this repair facility conduct work on any vehicles that are powered by (in part or totally) by Hydrogen, LP-Gas, CNG, or LNG vehicles?

If yes, Demonstrate compliance with NFPA 30A and the appropriate NFPA [Hydrogen – NFPA 2, LP – NFPA 58, CNG and LNG – 30A Section 7.8]

-----------------------------

Thursday, November 21, 2024 DF: RTC: No, this repair facility will not conduct work on any vehicles that are powered by (in part or totally) by hydrogen, LP-Gas, CNG, or LNG.

11/22/2024 dfeagle

17) How will you make the floor of the Service areas and areas where Flammable and/or Combustible liquids will be stored “liquid tight”? 30A:7.4.3.2

-----------------------------

Thursday, November 21, 2024 DF: RTC: Floors where flammable and/or combustible liquids are stored are treated with Ashford Formula, which is a concrete densifier to make the concrete "liquid tight". A technical data sheet for this product has been included in this resubmittal for review.

11/22/2024 dfeagle

18) Sheets A201b and P201 shows a sloped area adjacent to the roll up doors with a drain. The rest of the service floor does not appear to be sloped. NFPA 30A:7.4.3.2, 30A:7.8.5.5

Show the Service Shop Floors sloping towards the floor drains.

-----------------------------

Thursday, November 21, 2024 DF: RTC: The service bays are unable to have sloped floors, due to use of vehicle lifts in the bays. A sloping floor would cause clearance problems between vehicle lift arms and the bottom of the vehicles. There is a drain at the roll up door where liquid could be pushed to if required. Spills on the shop floor are cleaned up immediately, to prevent any hazardous conditions at the work bays.

Monday, November 25, 2024 0830 hrs. DF: I spoke with Jiazhen Sun via phone regarding the floor drains and sloped floor. After discussion Jiazhen agreed to place a HOLD 105 (framing) Inspection for revision to place a trench drain in the center drive portion of the service bay.

11/25/2024 dfeagle

19) Will this facility work on vehicles with “Nonordorized” gases? If Yes, demonstrate compliance with NFPA 30A:7.4.6.

-----------------------------

Thursday, November 21, 2024 DF: RTC: This facility will not work on vehicles with "non-odorized" gases.

11/22/2024 dfeagle

20) Will there be a parts cleaner on site? If Yes, The solvent shall be nonflammable and have a flash point above 100°F. NFPA 30A:9.76.

Provide information on the parts cleaner and solvent demonstrating compliance with 30A:9.7.6.

-----------------------------

Thursday, November 21, 2024 DF: RTC: The owner does not intend to use an on-site parts cleaner.

11/22/2024 dfeagle

21) Exit signs on the LSP and Electrical Sheets do not match. The exit signs are installed from the electrical Sheets. Match the LSP and Electrical Sheet Exit Signs.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Noted. Exit signs on LSP, "OCCUPANCY & EGRESS DIAGRAM (FBC/FFPC) - LEVEL 1" & "OCCUPANCY & EGRESS DIAGRAM (FBC/FFPC) - LEVEL 2" on Sheet G003 match "LEVEL 1 LIGHTING PLAN" & LEVEL 2 MEZZANINE LIGHTING PLAN" on Sheet E301.

11/22/2024 dfeagle

22) It does not appear that the egress paths in the following areas are provided with emergency lighting. 101:40.2.9

Service Drive 129, Roll up door side of Service Shop 132, Sprinkler Room 134, Comp/Fluids 133 and Tools 137, Outside of Exit Doors 132b and 132e.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Noted. Please see Sheet E301 - service drive lighting has been indicated with integral backup, keynote L2, Fixture XE added to sprinkler and comp fluids room.

11/22/2024 dfeagle

23) I am not able to determine if the Emergency Lighting coverage provides 1 ft-candle along the egress paths. 101:7.9.2.1.1.

Provide Emergency Lighting Photometrics demonstrating compliance with 101:7.9.2.1.1.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Noted. Emergency Lighting Photometrics along the egress paths has been provided on "E302 - EGRESS LIF+GHTING PHOTOMETRICS".

11/22/2024 dfeagle

24) Missing exit signs for Doors 132b and 132e.

-----------------------------

Thursday, November 21, 2024 DF: RTC: Noted. Exit sign has been added to Doors 132b and 132e on "LEVEL 1 LIGHTING PLAN", Sheet E301.

11/22/2024 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:

- Fire Alarm System [E401](all sprinkler control valves and the BFP to be electronically supervised [Fire Marshal Directive 22-001]
- Fire Sprinkler System (HVLS Fans-A301)
- Fire underground
- Above/Underground Storage Tanks
-
-
-
-

 

11/22/2024 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Air handlers with more than 2000 CFM are required to have duct smoke detectors. NOTE: If there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. 90A:6.4
Where smoke detectors required by 6.4 are installed in a building not equipped with an approved fire alarm system as specified by 6.4.4.2, the following shall occur:
1. Smoke detector activation required by section 6.4 shall cause a visual signal and an audible signal at a normally occupied area.
2. Detector troubles shall be indicated visually or audibly in a normally occupied area identified as air duct
</spa

11/22/2024 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:  NFPA 101 7.9.2.3
(1) Failure of a public utility or other outside electrical power supply
(2) Opening of a circuit breaker or fuse
(3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities.
NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2.

11/22/2024 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Buildings containing Fire Alarm Systems, Fire Sprinkler Systems, etc. and/or Security Systems that make it difficult to access the building in an emergency are required to have a Fail-Safe box. NFPA 1:18.2.2.1

Please contact St Johns County Fire Rescue Secretary Dawn Lyons at 904-209-1712 for the correct order form.

11/22/2024 dfeagle