Plan reviewed for New BDA located in Dry Pipe Closet 126. System consists of FLEX HONBDA 7S (BDA/Battery, Annunciator, Dedicated Remote Annunciator (HONBDA-BTTY-ANN-6 located at the FACP and one to be located at the FACP Remote Annunciator.
Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
-------------------------
Friday, April 4, 2025 DF: Review of 1st Resubmittal.
|
4/4/2025
| dfeagle |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 8th Ed.
|
4/4/2025
| dfeagle |
|
|
1) I Do not see a BDA Remote Annunciator at the FACP Remote Annunciator. 1225:18.4.2
Provide a dedicated remote annunciator at the location of the FAP's Remote Annunciator.
-------------------------
Friday, April 4, 2025 DF: RTC: Additional BDA annunciator added next to Fire Alarm Annunciator on vertical diagram page BDA-02 and plan on page BDA-05.
|
4/4/2025
| dfeagle |
|
|
2) The 800MHz Heat Map on Sheet BDA-07 is in black and white.
Provide the heat map in color format.
-------------------------
Friday, April 4, 2025 DF: RTC: Plans will be printed in full color for the new submittal.
|
4/4/2025
| dfeagle |
|
|
3) I do not see in the Riser Diagram connectivity to the building Fire Alarm System for monitoring the BDA System. 1225:18.14.1
Show the monitoring of the BDA System in accordance with 1225:18.14.1
-------------------------
Friday, April 4, 2025 DF: RTC: Monitoring and supervisory diagrams have been added on page BDA-02.
|
4/4/2025
| dfeagle |
|
|
4) St Johns County uses NFPA 1225 2022 edition. The applicable codes references NFPA 1221.
Update the code reference to the 2022 edition of NFPA 1225 and verify the plans comply with NFPA 1225.
-------------------------
Friday, April 4, 2025 DF: RTC: Codes have been updated on page BDA-01 to reflect 2022 NFPA 1225.
|
4/4/2025
| dfeagle |