Plan reviewed for New Fire Sprinkler System consisting of a Fire Pump, Nitrogen Generator Corrosion Monitoring System, Wet and Dry Systems.
Above Ground Fire Sprinkler System connecting at 1’ AFF to the underground 10” Fire Line to a 2,000 GPM Model 1823BF horizontal split case Electric Fire Pump. To a 10” manifold with two (2) 6” wet Risers, one (1) 8” Riser and one (1) 4” Riser. The 6” remote FDC connecting to post Fire Pump at 10” Fire Pump bypass
System #1: 6” Wet Riser to Zone #1 [40,016 SF], transitioning to a 2 ½” Dry Pipe protecting the Drive-Through Canopy.
System #2: 6” Wet Riser to Zones #2 [40,297 SF].
System #3: 8” Wet Riser to 44,201 Sf [44,201 SF], transitioning to a 6” Dry Pipe System with a Nitrogen Generator Monitoring System [Engineered Corrosion Solutions AG-2000] protecting the Garden Center.
System #4: 4” Wet Riser to In-Rack Sprinkler Zone.
Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.