| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for 136,228 SF Type IIB(II(000)) Construction, Sprinkled (w/Fire Pump), BDA, Fire Alarm System Throughout, Sprinkled, NFPA 110 Generator.
Reviewed as Class A Mercantile – Bulk Merchandising Retail Building
Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
--------------------------------
Thursday, February 1, 2024 DF: Review of 1st Resubmittal
--------------------------------
Tuesday, April 2, 2024 DF: Review of 2nd Resubmittal.
--------------------------------
Friday, April 12, 2024 DF: Review of 3rd Resubmittal.
|
4/12/2024
| dfeagle |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 7th Ed.
|
4/12/2024
| dfeagle |
|
|
1) This is a preliminary review. Do not resubmit until clearance sheet and approved site plan obtained. Turn in both clearance sheet and approved site plan with building permit application to Fire Permit Tech.
NOTE: Based on fire's site review, additional comments may be provided.
|
2/1/2024
| dfeagle |
|
|
2) The two sets of plans are loose leaf and not bound (staples, pinned, etc.). The plan sets are to be bound upon resubmittal.
|
2/1/2024
| dfeagle |
|
|
3) The plans code references are primarily based on the Florida Building Code (FBC). I am not seeing code references from the Florida Fire Prevention Code 7th Ed. (FFPC).
Provide FFPC references with each FBC reference. This can be done separately of parallel to the FBC references.
--------------------------------
Thursday, February 1, 2024 DF: RTC: Reference T1.01 for Florida Prevention Code 7th listed on the title Sheet and code reference about Class A Mercantile per FFPC 36.1.2.2.1.
|
2/1/2024
| dfeagle |
|
|
4) There are numerous Civil Sheets included in the plan set. Civil Sheets are used during the Development Review Committee process. They are not to be a part of the building plan review process.
Remove ALL Civil Plan Sheets from the building plan sets.
|
2/1/2024
| dfeagle |
|
|
5) The following will be required to be submitted as Deferred Submittals for permits:
a) Fire Sprinkler System
b) Fire Alarm System
c) Fire Pump
d) Emergency Responder Communication Enhancement System (AKA Building Radio Enhancement System or/ “BDA”)
e) Generator
|
2/1/2024
| dfeagle |
|
|
6) Sheet A4.07 indicates that a generator or generator’s will be installed adjacent to the Electrical room. The Emergency Lighting (EL) Sheets and electrical Panel “EM” indicates the generator will be used for powering specific normal egress lighting fixtures as Emergency Lighting.
New Emergency Power Systems for Emergency Lighting shall be at least Type 10, Class 1.5, Level 1 in accordance with NFPA 110. 101:7.9.2.2
Provide documentation for the generator system demonstrating it complies with 101:7.9.2.2
--------------------------------
Thursday, February 1, 2024 DF: RTC: Reference generator submittal documentation for validation the system complies with NFPA 7.9.2.2.
Thursday, February 1, 2024 DF: Reviewer's Response: Generator Documentation (Part of Clearance Sheet C23-7946*1 Review) indicates the generator is capable of being NFPA 110 Level 1 compliant when equipped with necessary accessories and installed in accordance per NFPA Standards. The Generator documentation lists the requirements on Sheet #2 of the Generator Set Accessories document.
The generator will be reviewed for compliance under Clearance Sheet C23-7946*1.
|
2/2/2024
| dfeagle |
|
|
7) Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following: NFPA 101 7.9.2.3 (1) Failure of a public utility or other outside electrical power supply (2) Opening of a circuit breaker or fuse (3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities. NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2.
--------------------------------
Thursday, February 1, 2024 DF: RTC: Reference E6.01 for updated emergency lighting fixtures in the light fixture schedule and on lighting plan Sheets E1.11 and E4.11 to include battery back ups (Fixture types B and C), Alternating generator backed up circuits are provided on garden center lighting plan E1.22 and for canopies on lighting plan E1.11 to comply in case of an accidental opening of a circuit breaker. Additional battery backed up wall packs are provided as well in lighting plan E1.11 and Garden Center lighting plan E1.22 as well to meet requirements.
|
2/2/2024
| dfeagle |
|
|
8) With exception of the Garden Center, the Exit Signs throughout are indicated on Sheet E6.01 as being “Photoluminescent”. Photoluminescent exit signage is permitted, provided the face of the exit sign be continually illuminated in accordance with the signs listing. The charging illumination shall be a reliable light source such as a non-switched night light, and meeting the listing requirements for the type of illumination. 101:36.2.10
There are some of the night lights located at, near, or in the area of the photoluminescent exit signs. However, there are photoluminescent exit signs not covered by the night lights. I am unable to determine it the night lights comply with the manufactures listing. 101:7.10.7.2
a) Provide the manufacturer’s specification sheet(s) for the photoluminescent exit signs, AND
b) Evaluate the locations of the night lights for compliance with the mfr.’s spec sheets for compliance with the illumination requirements for the signs, AND
c) adjust the lighting sheets to demonstrate compliance with 101:7.10.7.2
--------------------------------
Thursday, February 1, 2024 DF: RTC: Reference E4.11 for updated emergency lighting on enlarged lighting plan in restroom vestibule and COS room so all photoluminescent exit signs will be covered. A photometric to show the photoluminescent exit signs will be lit in an emergency setting is provided in submittal. Night Lighting reference was removed from Sheets, because emergency lighting fulfills owner's night lighting requests.
Thursday, February 1, 2024 DF: Reviewer's Response:
a) I did not see the Manufacturer's Specification Sheets for the Photoluminescent Exit Signs. Provide the spec sheets for the exit signs so I can verify the lumens and ft-candles freguired.
b) The Photometrics provide are on 8.5" x 11" sheets. They are difficult at best to see the photometrics. Provide the Summary and Area Layout Photometrics Sheets on larger Sheets so the documentation is legible.
--------------------------------
Tuesday, April 2, 2024 DF: RTC: Refer to manufacturer's specification sheet for photoluminescent exit sign attached with lumens and ft-candles. The photometrics are reprinted on 24"x36" paper size for legibility in review.
Tuesday, April 2, 2024 DF: Reviewer's Response: Only one (1) copy of the Photometrics provided. Submitted for scanning as "Office Copy" Photometrics demonstrated the minimum 5 ft-candles met.
|
4/3/2024
| dfeagle |
|
|
9) Fire Protection Sheet FP1.0 indicates the Hydrant Flow Test dated 12/05/2022. By the time this permit will be at the approval point the hydrant flow test will more than a year old.
Have the FP Engineer update the hydrant flow test data with a test date less than one year old. The FRE will also need to reevaluate the Fire Protection data / sheets to the new hydrant flow test data.
--------------------------------
Thursday, February 1, 2024 DF: RTC: Reference FP1.0 for data updates resulting from the new hydrant flow test conducted 01/16/2024 by Wayne Automatic Fire Sprinklers, Inc.
Thursday, February 1, 2024 DF: Reviewer's Response: Flow data on Sheet FP1.0 has an actual Flow Date of 12/19/23. Within the one year requirement.
|
2/2/2024
| dfeagle |
|
|
10) Sheet A2.01, Keyed Note #37 indicates a “KNOX” box to be installed. St Johns County uses “FAILSAFE” Brand building access boxes for building access. Please contact Dawn Lyons at 904-209-1712 or dlyons@sjcfl.us for the FAILSAFE order form and to help with any questions you may have.
--------------------------------
Thursday, February 1, 2024 DF: RTC: Refer to A2.01 for Knox Box specification added to Keynote #37 as required by St Johns building access. FAILSAFE used, and contact information provided to General Contractor to order and coordinate installation.
|
2/2/2024
| dfeagle |
|
|
11) Sheet A2.01 indicates there is a trash compactor chute opening into receiving Area 125. The trash compactor chute opening does not open into an intake room as required by NFPA 82:8.3.5. 101:36.5.4, 101:9.5.1.3
a) Show the compactor chute door opens in a rated intake room, and is lockable. 101:36.5.4 and 82.8.3.5
--------------------------------
Thursday, February 1, 2024 DF: RTC: Trash compactor chute does not connect more than one level and does not have a vertical condition that would cause fire spread. The lockable chute door has a diagonal chute that feeds directly into the compactor located within the truck dock area.
Thursday, February 1, 2024 DF: Reviewer's Response: NFPA 101:9.5.1 requires the Trash Chute opening to be contained within a room separate from the rest of the building / areas in accordance with Section 9.5 of NFPA101 and NFPA 82. 101:9.5.1, NFPA 101:9.5.2.
Provide plans demonstrating compliance with NFPA 101:9.5 and NFPA 82.
NOTE: Clearance Sheet C23-7946*2 has been submitted for review of the Trash Compactor. The Compactor Chute Door and the Intake room will remain under this Clearance Sheet (C23-7946). The installation of the compactor will fall under Clearance Sheet C23-7946.2.
--------------------------------
Tuesday, April 2, 2024 DF: RTC: Please review the emailed argument against the need for a lockable, rated intake room. The Home Depot has thousands of properties across the United States without intake rooms. The configuration commonly used is considered "External Waste Compactor" with hopper which does not carry the requirements of a "Chute" per the NFPA.
Tuesday, April 2, 2024 DF: Reviewer's Response: FM Dowling and Reviewer Dan Feagle participated in a Microsoft Teams Meeting at 1300 with Suzanne Berkey (Project Manager), The FPE, Architect of Record and a couple of other representatives regarding the Intake Room requirement of the Trash Compactor Cute Door area. The representatives are putting together a Alternate Methods Letter for the FM to remove the Intake Room requirement by adding a sprinkler head in the hopper, a heat detector in the Chute and making the Chute Door Fire Rated 1.5 hrs. and provide the Chute Door with a Smoke Seal.
FM Dowling said to present the Alternate Method Letter and he will make a decision on the Intake Room.
I will hold the plans in my office until COB this Friday 04/05/2024
--------------------------------
Friday, April 12, 2024 DF: An Alternate Means & Methods (AM&M) proposal has been submitted to Fire Marshal R. Dowling as an alternative to satisfy the protection requirements of Section 9.5 of NFPA101 and NFPA 82. 101:9.5.1, NFPA 101:9.5.2, NFPA 82.3.2, 82:6.2.3.3 as noted in Comments #11 and #12. The AM&M has been submitted for scanning and a copy will be provided with the approved plans set to be on site.
A copy of the approved AM&M is to be provided by sprinkler contractor along with the Fire Sprinkler Plan Submittal.
|
4/12/2024
| RDowling |
|
|
12) Provide the manufacturer’s specification sheet for the compactor chute door demonstrating it complies with 82.3.2.
--------------------------------
Thursday, February 1, 2024 DF: RTC: See attached for Manufacturers specification Sheet.
Thursday, February 1, 2024 DF: Reviewer's Response: The Mfr. Spec Sheet provided identifies the Trash Compactor as a PTR Baler & Compactor Model TP-4000HD and provides dimensional information and provides dimensional measurements only. The Spec Sheet does not provide information regarding the door requirements of NFPA 82.3.2, 82:6.2.3.3.
Provide the information regarding the Chute's Door needed to satisfy 82:3.2.
NOTE: Clearance Sheet C23-7946*2 has been submitted for review of the Trash Compactor. The Compactor Chute Door and the Intake room will remain under this Clearance Sheet (C23-7946). The installation of the compactor will fall under Clearance Sheet C23-7946.2.
--------------------------------
Tuesday, April 2, 2024 DF: RTC: See above. The Home Depot has thousands of properties across the United States without fire rated doors for the "External Waste Compactor" with hopper. The exterior wall is not required to be fire rated assembly due to any building separation or building type requirements. To satisfy this comment, a custom fire rated door may be provided from another vendor that will replace the commonly installed compactor door. Please find the cut sheets available from the vendor.
Tuesday, April 2, 2024 DF: Reviewer's Response: FM Dowling and Reviewer Dan Feagle participated in a Microsoft Teams Meeting at 1300 with Suzanne Berkey (Project Manager), The FPE, Architect of Record and a couple of other representatives regarding the Intake Room requirement of the Trash Compactor Cute Door area. The representatives are putting together a Alternate Methods Letter for the FM to remove the Intake Room requirement by adding a sprinkler head in the hopper, a heat detector in the Chute and making the Chute Door Fire Rated 1.5 hrs. and provide the Chute Door with a Smoke Seal.
FM Dowling said to present the Alternate Method Letter and he will make a decision on the Intake Room.
I will hold the plans in my office until COB this Friday 04/05/2024.
--------------------------------
Friday, April 12, 2024 DF: An Alternate Means & Methods (AM&M) proposal has been submitted to Fire Marshal R. Dowling as an alternative to satisfy the protection requirements of Section 9.5 of NFPA101 and NFPA 82. 101:9.5.1, NFPA 101:9.5.2, NFPA 82.3.2, 82:6.2.3.3 as noted in Comments #11 and #12. The AM&M has been submitted for scanning and a copy will be provided with the approved plans set to be on site.
A copy of the approved AM&M is to be provided by sprinkler contractor along with the Fire Sprinkler Plan Submittal.
|
4/12/2024
| RDowling |
|
|
13) There are several doors with Delayed-Egress Electrical Locking Systems and a few doors with magnetic locks. All of these doors have panic hardware also. These doors with special locking arrangements will not be reviewed at this time. 101:36.2.2.2
NOTE: It appears that there are doors with Delayed-Egress Electrical Locking Systems that required you to
I am placing a HOLD 105 (framing) Inspection for a revision for Special locking arrangements to address these and any other door with special locking arrangements.
--------------------------------
Thursday, February 1, 2024 DF: RTC: Acknowledged this will be an inspection item.
Thursday, February 1, 2024 DF: Reviewer's Response: The following doors were identified on Sheet A6.01 and the Project Book Section 087000 as having Special Locking Arrangements such as Delayed-Egress Electrical Locking Systems (101:7.2.1.6.1), Sensor-Release of Electrical Locking Systems (101:7.2.1.6.2, Mag-Locks, Etc.
Door #'s: 101C, 101D, 101E, 101G, 101H, 101J, 101K, 101M, 101N, 115A, 124A, 125A, 127A, 127F, 130A, AND 130B.
These doors and any other door not noted herein that has special locking arrangements, mag-locks, etc. are required to be provided for review as a revision to approved plans. Provide a Floor Plan showing the locations of each Door noted below with Special Locking Arrangements along with Mfr. Spec Sheets for the locking arrangement and demonstrating the locking arrangement complies with 101:7.2.1.6.1 and 101:7.2.1.6.2 or other section of 101:7.2.1.
--------------------------------
Tuesday, April 2, 2024 DF: RTC: Home Depot elects to remove Delayed-Egress from this project to prevent the need for future review or discussion. Please, find the attached manufacturer spec sheets for the non-delayed egress hardware for review and A6.01 updated to reflect this change.
Tuesday, April 2, 2024 DF: Reviewer's Response: FM Dowling and Reviewer Dan Feagle participated in a Microsoft Teams Meeting at 1300 with Suzanne Berkey (Project Manager), The FPE, Architect of Record and a couple of other representatives regarding the Intake Room requirement of the Trash Compactor Cute Door area. Also discussed Doors 125A and 130A regarding the latch retraction and if the hardware is mechanical free egress. Per the architect and EOR the panic hardware will be mechanical free egress with electric latch retraction on the ingress side only.
|
4/3/2024
| dfeagle |
|
|
14) The Door and Hardware Schedule on Sheet A6.01 identifies doors that have Delayed-Egress that the Project Manual Hardware Page does not identify by door number. For example; Project Manual identifies Door #130A only for hardware set #14 and Sheet A6.01 identifies Doors 130A, 130B and 131B as having Hardware Set #14. This has been noted throughout the Project Manual and Door and Hardware Schedule on Sheet A6.01.
Update the Project manual; and/or Sheet A6.01 so the correct doors are identified.
--------------------------------
Thursday, February 1, 2024 DF: RTC: Door tag numbers revised to coordinate with the project manual (#131A, #132B). Update clouded on A6.01 detail 1 upper left corner. The door and hardware set schedule updated accordingly.
Thursday, February 1, 2024 DF: Reviewer's Comment: See Reviewer's Response to comment #13.
|
2/2/2024
| dfeagle |
|
|
15) Door 131B from the TRC Maintenance Room 131 as having Delayed-Egress (Hardware Set #14. Having Delayed-Egress on this door places the occupant having to travel through two doors with Delayed-Egress. This will require complying with 101:7.2.1.6.1.1(3). This will need to be addressed during the revision review for Special Locking Arrangements noted above.
--------------------------------
Thursday, February 1, 2024 DF: RTC: Door numbers revised to coordinate with project manual (131A). Updated clouded on A60.01 detail 1 upper left corner. The door and hardware schedule updated accordingly. Hardware set for door #131A to #11 which does not contain Delayed-Egress and coordinates with the Project Manual.
|
2/2/2024
| dfeagle |
|
|
16) The Exterior Electrical Room #124’s two exit doors 124A and 124B are shown with Hardware Set #03 (cylinder core / padlock. These doors require panic hardware. NFPA 70:110.33(A)(3); NFPA 70:110.26(C)(3) (electrical equipment >1,000V and/or >800 Amps)
Provide panic hardware for these two doors.
--------------------------------
Thursday, February 1, 2024 DF: RTC: Hardware Set for doors #124A and 124B revised to #8 and #10 respectfully on A6.01 which utilizes an exit device. Updates are made to the door hardware specification including the hardware sets reviewed by consultant DH Pace.
|
2/2/2024
| dfeagle |
|
|
17) The double fence gate #101L at the left rear of the Secure Tool Storage is shown in the Hardware Schedule to have a padlock. The LSP does not show this gate to be a part of the means of egress. This gate will need “NOT AN EXIT signage complying with 101:7.10.8.3 installed on the gate so that it is visible to the Tool Storage side when closed.
Provide a sample of the signage complying with 101:7.10.8.3.
--------------------------------
Thursday, February 1, 2024 DF: RTC: Refer to A6.01 for added door schedule note #23 that calls for the NOT AN EXIT sign to be provided and installed by GC with a description. A boxed note is also added to T1.02 Life Safety Plan indicated on plan pointing to the double fence gate. Shelving heights will prevent customers outside Shelving units will prevent customers outside the STS from seeing the EXIT sign unless they are unless they are within the space.
|
2/2/2024
| dfeagle |
|
|
18) The Secure Tool Storage section needs Exit Signage inside the Secure Tool Storage (STS) area to guide the occupants to the only two exits from the STS area. The EXIT signage will need to be installed so that the exit signage is visible from within the STS area but will not confuse the other occupants of the main store area outside the STS area. 101:36.2.10
Demonstrate compliance with this requirement
--------------------------------
Thursday, February 1, 2024 DF: RTC: Refer to T1.02 for exit signage visible within the STS area. Also reference E1.1 for added exit signage to lighting plan at the two exits inside the Secure Tool Storage,
|
2/2/2024
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- Fire alarm system - Fire sprinkler system (Also see comment #12 & #13) - Fire underground - Fire Pump - Generator - HOLD 105 (Framing) INSP - Revision for Special Locking Arrangements - In-Building Radio Enhancement System (BDA) TEST / PERMIT - - - -
|
2/1/2024
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Air handlers with more than 2000 CFM are required to have duct smoke detectors. NOTE: If there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. (NFPA 90A:6.4.4.2) Where smoke detectors required by 6.4 are installed in a building not equipped with an approved fire alarm system as specified by 6.4.4.2, the following shall occur: 1. Smoke detector activation required by section 6.4 shall cause a visual signal and an audible signal at a normally occupied area. 2. Detector troubles shall be indicated visually or audibly in a normally occupied area identified as air duct
|
2/1/2024
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following: NFPA 101 7.9.2.3 (1) Failure of a public utility or other outside electrical power supply (2) Opening of a circuit breaker or fuse (3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities. NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2
|
2/1/2024
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Occupancy Sensor NFPA 101: 7.8.1.2.2 Unless prohibited by Chapters 11 through 43, automatic lighting control devices shall be permitted to temporarily turn off the illumination within the means of egress, provided that each lighting control device complies with all of the following: (1) In new installations, the lighting control device is listed. (2) The lighting control device is equipped to automatically energize the controlled lights upon loss of normal power and is evaluated for this purpose. (3) Illumination timers are provided and are set for a minimum 15-minute duration. (4) The lighting control device is activated by any occupant movement in the area served by the lighting units. (5) In new installations, the lighting control device is activated by activation of the building fire alarm system, if provided. (6) The lighting control device does not turn off any lights relied upon for activation of photoluminescent exit signs or path markers. (7) The lighting control device does not turn off any battery-equipped emergency luminaires, unit equipment, or exit signs.
Be Prepared to Show Compliance at the time of your Fire Alarm Final or Fire Final.
|
2/1/2024
| dfeagle |
|
|
19) Friday, February 2, 2024 New Comment based on 1st Resubmittal Review.
One (1) set of plans for XXX Clearance Sheets (C2013-). This comment will not be signed off until all Clearance Sheets have all of their comments addressed.
|
4/12/2024
| dfeagle |