SJC Home
Clearance Sheet C2023-006739

 Department IssuesSigned OffIntl

Plans for 2500sf Starbucks shell building. The building is VB construction and is not indicated to have a fire alarm of fire sprinkler system.  Plan submitted and reviewed as assembly.  A separate permit will be required for the interior remodel. 

Note: No panic hardware is indicated.  Will verify occupant load when buildout permit is submitted.


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

1/8/2024 PWebb

Informational note:

The floor plan indicates an automatic front door.  The door schedule does not reflect this.  If this is included in the buildout plan, it will be reviewed at that time. 

1/8/2024 PWebb