| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for 7 device monitored fire alarm system to monitor sprinkler and control HVLS fan shut down. Reviewed as using FFPC 8th edition effective January 1, 2024. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Reviewer: V.Vitori For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us. To schedule fire inspections call 827 6842 (automated system). Questions about inspections or resubmitting your plans call 209 1740x1.
|
| |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 8th Ed.
|
| |
|
|
1) DO not see where the sprinkler valves (backflow or PIV) are electronically supervised. 101:6.1.14.4.1(b) 101:38.3.6.1 101:42.2.5
Wednesday, October 2, 2024 "PIV" shown on page 3. Inspector just make sure that outside sprinkler valves have tampers.
|
10/2/2024
| VVitori |
|
|
2) Either:
a) make sure door to FACP room is labeled from outside and access key to this door is placed in Fail Safe box OR
b) add annunciator within 10' of front door with access key to this door placed in Fail Safe box.
Wednesday, October 2, 2024 Response to comment indicates "In lieu of an annunciator at the entry door the FACP has been moved to the main entry which has a built in annunciator that is fully functional and is protected by a door with key just like the annunciator".
FACP now located within 10' of panel entry.
|
10/2/2024
| VVitori |
|
|
Tuesday, August 20, 2024 PJW- Tori, I just reviewed a revision to add the 1 and 2 family dwelling back to the first floor. Take a look at my revision to make sure the space is covered.
|
10/2/2024
| VVitori |
|
|
Newly added comment 10/2/24 based on resubmittal of drawings.
3) Looking at newly provided page 3, HVLS fans no longer show they are tied into a fire alarm relay as shown on prior plans. 101:6.1.14.4.1(b), 101:38.3.6.1, 101:42.2.
Wednesday, October 2, 2024 10:59:56 AM I called contact to ask if they could update the plan to show it again. Brad the owner of GC co. and architectural firm said they are not HVLS fans they are only 52" across! I said according to A1.0 (I am guessing I measured fans since I don't see a fan equipment schedule) they do meet the requirements of HVLS via size. I asked if he could point out in approved plans (what page and detail) indicates size or model. He couldn't find it either. I offered if he sent me an email stating what size the fans area I would not reject the fire alarm again.
Monday, October 7, 2024 Received email this morning that 56" industrial fan will be used. Email and spec sheets printed and turned in to be scanned.
|
| |