Plans for a revision to the following sheets: T1.0, LS1.0, A1.0, A1.1, A1.2, A2.0, A2.1, E001, E101, E102, E200, E201, E2l2, E300, E302, P001, P002, P003, and P004. The revision is to add a security guard living space, add rated windows to a rated wall, add a washer/dryer and janitors sink. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

 

1) Either smoke alarms or a smoke detection system is required per NFPA 101:24.3.4.1.  Indicate which option you are choosing and demonstrate compliance with the requirements as applicable.  NFPA 101:24.3.4.1.1, 24.3.4.1.2.   

 

2) Carbon monoxide alarms are required per NFPA 101:24.3.4.2.1 unless exempted.  Provide alarm or provide code path for exemption.

 

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:


- Fire Sprinkler System must be revised to include the changes to the floor plan.