SJC Home
Clearance Sheet C2023-000817

 Department IssuesSigned OffIntl

Plan reviewed for New Fire Alarm System: Notifier FACP N16 s/x, Notifier Remote Annunciators: RLD, Honeywell Gateway: HON-CGW-MBB, Honeywell Communicator 4G LTE: ATT-HON.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

---------------------------

Wednesday, December 13, 2023 DF: Review of 1st Resubmittal.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 7th Ed.

 

1) There are several locations including offices that do not have visual notification devices. 101:9.6.3.5

The following locations need visual notification devices: Business Office 202, Vestibule 278, Offices 248, 249, 253, Providers Offices: 206, 207, 208, 209, 210, 242, 243, 244, 245, 246, 247, 257, 258, 286, 287, and 288.

Add visual notification devices in these locations.

---------------------------

Wednesday, December 13, 2023 DF: Business Office 202 still without visual notification device.

 

2) Wednesday, December 13, 2023 DF: New comment based on review of 1st Resubmittal. Sheet FA-2 appears to be different from the originally submitted Sheet FA-2. Office 248 and 249 have been combined and are now Conference Room 248-1. Office 253 has been divided into Staff Toilet 249 and Storage 253. Storage 252 has been enlarged consuming the space between Storage 252 and Office 202.

I have found no revision to the building plans for these changes. If these changes noted above on the Fire Alarm Plan are correct state so in your response to comments and provide details response to comments regarding the changes in the spaces. If not, update the drawings to reflect the approved construction plans.