SJC Home
Clearance Sheet C2023-000817

 Department IssuesSigned OffIntl

Plan reviewed for New NFPA 110 Type 1, Level 10, Class X (128 hr.) Outdoor Emergency Power Generator: Generac SD400, 400 kW Diesel Generator, Fuel Tank: 3,550 Gallons - 90% usable capacity, 4,033 Gallons 100% capacity. Run Time 96 hrs. + 33% (128 Hrs.)

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 7th Ed.

 

1) I am not able to find documentation verifying the Level, Type and Class this Generator is in accordance with NFPA 110 Chapter 4.

Provide documentation demonstrating the Class , Type and Level this generator is classified as per NFPA 110 Chapter 4..

 

2) Provide a Floor Plan Sheet showing the location for the Remote Annunciator, transfer equipment, etc. 

 

3) The Emergency Generator shall be monitored by the Fire Alarm System for a) Generator Running, b) Generator Fault, and c) Generator Switch in Nonautomatic Position. 101:9.1.3.2

A HOLD Fire Final for Fire Alarm Revision demonstrating the FA system is monitoring the above noted generator items.