SJC Home
Clearance Sheet C2022-007887

 Department IssuesSigned OffIntl

Plan submitted for new 8476sf sprinklered construction type IIB shell building with 3 demising walls creating 4 suites (101-104). Reviewed as new shell using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

11/2/2022 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

11/2/2022 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) a permit has been pulled :
- Fire alarm system (supervised because shell with separate tenant spaces, also design criteria on FA pages)
- Fire sprinkler system
- Fire underground (plus new hydrant)

11/2/2022 VVitori

1) This is a preliminary review. Do not resubmit until clearance sheet obtained and approved site plan included.

NOTE: Based on fire's site review, additional comments may be provided.

11/2/2022 VVitori