| | Department Issues | Signed Off | Intl |
|
|
Plans for a 12'6" CaptiveAire Hood, model 5424 ND-2-PSP-F. Makeup air will be climate controlled. The duct will be single wall DW18 duct.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code. For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.
|
| |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 8th Ed.
|
| |
|
|
1) What is the wall behind the hood and the cooking equipment constructed of? Demonstrate compliance with NFPA 96:4.2 or 4.2.3 all the way from the top of the hood to the floor.
Info Note: Even with metal studs, 3” clearance is required to gypsum wall board. Most hoods have a 3” standoff built in, however the same must be provided all the way to the floor.
Sheet 2 indicates an insulated backsplash. Is this intended to serve as a clearance reduction method per NFPA 96 section 4.2.3? If yes, indicate this and indicate which specific one you meet.
|
| |
|
|
2) Provide a roof plan view indicating the clearances to the items indicated in NFPA 96:7.8.2.1.
|
| |
|
|
3) The duct indicated is single wall listed duct. Demonstrate clearance to combustibles. If you plan on wrapping the duct to reduce clearances, provide specifications for the proposed wrap. NFPA 96:4.2.1
|
| |
|
|
4) Provide a floor plan identifying the location of the hood(s) in the building.
|
| |