| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for Buildout of Fast Food Restaurant, 1,996 SF, Type IIB(II(000)) Construction, Sprinkled, No Fire Alarm noted,
Reviewed as Class C Mercantile Dining Room Occupant Load 49.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
----------------------------
Wednesday, January 24, 2024 DF: Review of 1st Resubmittal.
|
1/24/2024
| dfeagle |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 7th Ed.
|
1/24/2024
| dfeagle |
|
|
1) I am only able to find one means of egress from the dining area. 101:12.2.4.1
Provide a second means of egress from the Dining Room.
----------------------------
Wednesday, January 24, 2024 DF: RTC is lengthy. In summary, the dining room was modified and the occupant load is now 49. Class C Mercantile. Single exit permitted. RTC submitted for archival.
|
1/24/2024
| dfeagle |
|
|
2) The corridor from the Dining Room to the bathroom is 24’. Max length is 20 per 101:12.2.5.1.3.
Adjust the plans so the max travel distance is 20’ or less.
----------------------------
Wednesday, January 24, 2024 DF: Dead-End Corridor modified and is now 17'-11".
|
1/24/2024
| dfeagle |
|
|
3) The Type 1 Hood and its Suppression system is to be deferred submittals and Inspection holds have been placed for them.
There are several Sheets with Type 1 Hoods and suppression information on them. You will either have to remove the sheets or provide statement on the Sheets such as “DEFFERRED SUBMITTAL”, or “FOR INFORMATION ONLY”.
Sheets affected are: M-4, H1, H2, H3, H4, and H5.
----------------------------
Wednesday, January 24, 2024 DF: RTC: For Reference Only/Deferred Submittal has been added to Title Block of applicable sheets.
Wednesday, January 24, 2024 DF: Reviewer's Response: The Sheets noted above have not been updated with the language noted in the RTC. I am marking these Sheets as "NOT PART OF THIS PERMIT".
|
1/24/2024
| dfeagle |
|
|
4) There is an 8’ HVLS fan in the dining area. This fan will have to be tied into the building Sprinkler Monitoring FACP to comply with NFPA 13:11.1.7.
A 109 HOLD INSP has been placed for a Fire Alarm Permit.
|
1/24/2024
| dfeagle |
|
|
5) Emergency lighting shown on Sheet E1 is provided by wall packs which are typically designed to be installed approximately 8’ AFF on the wall and provide an egress path 3’ or 6’ in width and 8’ or more to each side. The wall packs shown on this sheet are few and some are placed over equipment. There are areas that have little to no EL coverage.
a) Provide El coverage throughout the egress paths meeting 101:7.9, AND
b) Provide the manufacturer’s spec sheets so I can verify coverage, OR
c) Provide Emergency Lighting Photometrics demonstrating compliance with NFPA 101:7.9.2.1.1.
|
1/24/2024
| dfeagle |
|
|
6) How will you ensure the area in front of the electrical panels will remain clear of storage? NFPA 70:110.26(A)(1),(2),(3)
----------------------------
Wednesday, January 24, 2024 DF: RTC: Specification item #31 has been added to Sheet E6.
|
1/24/2024
| dfeagle |
|
|
7) Sheet K101 notes NUCO2 Tank System (alarm). However, there is information that is missing for it to be accepted as indicated. A revision will be required to show more system detail. Ensure that you indicate the CO2 line runs and locations, indicating whether they are run above ceiling or below the slab. If they are above the ceiling, any areas below the lines will need to be protected with sensors unless the CO2 line is installed in sealed conduit. Identify the location of the sensors, the control unit and the required strobes for occupant notification.
A hold has been placed on the permit for this revision.
|
1/24/2024
| dfeagle |
|
|
8) I was not able to locate any Carbon Monoxide Detectors/alarm in the kitchen and at the 1st supply register from the A/C RTU’s 1, 2 and 3. 101:12.3.4.4 Provide CO detectors in the location required by 101:12.3.4.4
|
1/24/2024
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following: NFPA 101 7.9.2.3 (1) Failure of a public utility or other outside electrical power supply (2) Opening of a circuit breaker or fuse (3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities. NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2.
|
1/24/2024
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- Fire sprinkler system - Above / Used Oil Storage Tank System - Kitchen hood - Kitchen suppression system - Fire Alarm - HVLS Fan Tied to Sprinkler Activation - Hold 109 Inspection for CO2 Detection/Alarm System - - - -
|
1/24/2024
| dfeagle |