| | Department Issues | Signed Off | Intl |
|
|
1. 2020 FBC-Building 1006.2.1 states that 2 exits from any space shall be provided where the design occupant load exceeds the values listed in Table 1006.2.1. The Table shows that the maximum occupant load for an Assembly occupancy is 49 for a space with 1 exit. Please refer to 2020 FBC-Building Section 1007 for the minimum separation distance required between the 2 exits.
|
| |
|
|
2. 2020 FBC-Building 1020.4 states that where more than 1 exit is required, the exit access shall be arranged such that there are no dead ends in corridors more than 20 feet in length. The corridor from the Dining Room to the Bathroom is approximately 24 feet.
|
| |
|
|
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
|
| |