Plan submitted for new 79 device voice evac monitored fire alarm system. Reviewed as using FFPC 8th edition effective January 1, 2024. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

9/11/2024 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

9/11/2024 VVitori

1) Do not see where HVLS fans tied in to shut down upon fire alarm receiving waterflow. 13:11.1.7 

Wednesday, August 21, 2024 Response to comment indicates "Note #8 added to plan notes and referenced on plan at fan location on revised sheet C-E3.3. Note states to shut dan down up fire alarm activation."

There are no CE pages submitted with this submittal. They are all FA pages. Articulate how/where this comment was addressed on FA pages.

Wednesday, September 11, 2024 Response to comment indicates "This is clouded with REV 2 on FA 1 and the modules are called out HVLS fan shutdown located in the Movement studio and fitness studio."

Confirmed on FA1 as rev2

9/11/2024 VVitori

2) Do not see where sensor controlled standard lighting has been tied in to turn on with fire alarm activation.  101:7.8.1.2.2(5)

Wednesday, August 21, 2024 Response to comment indicates "This requirement is noted on previously submitted sheets C-E3.1 and E-E3.2 note 4."

There are no CE pages submitted with this submittal. They are all FA pages. Articulate how/where this comment was addressed on FA pages.

Wednesday, September 11, 2024 Response to comment indicates "This is clouded with REV2 on FA1 and the modules are called out Lighting control located in the room next to Hobbies Arts and Crafts."

Confirmed on FA1 as Rev2.

9/11/2024 VVitori

3) Do not see where visible signals provided in office 102, director 103, and office 104. 101:9.6.3.5

Wednesday, August 21, 2024 Response to comment indicates "Visual notification devices added to requested rooms on revised sheet C-E3.3."

There are no CE pages submitted with this submittal. They are all FA pages. Articulate how/where this comment was addressed on FA pages.

Wednesday, September 11, 2024 Response to comment indicates "This is clouded as REV2 on FA 1."

Confirmed

9/11/2024 VVitori