Clearance Sheet C2021-003434*015

 Department IssuesSigned OffIntl

Plan submitted for build out of 1017sf for a new business in an existing construction type IIB sprinklered building. Reviewed as new mercantile class c using FFPC 8th edition effective January 1, 2024. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

3/8/2024 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

3/8/2024 VVitori

1) Looking at A0.1 this business space was provided with a 1 hour separation to the adjacent suite labeled as business. Our records show suite 106 as a mercantile and suite 4 as an assembly.

a) show correct/updated occupancy classes for adjacent suite and suite to the rear of this unit.

b) show separation between occupancies as allowed by 101:6.1.14.4.1(a).

NOTE: If you choose to take the 1 hour reduction in separation allowed by 101:6.1.14.4.1(a), upon resubmittal make sure to provide documentation on fire alarm  or sprinkler contractor letter head from the respective contractor that sprinkler system is electronically supervised (including the backflow preventer and/or PIV's). 101:9.7.2.1.1

Friday, March 8, 2024 Response to comments indicate "Occupancy Separation: Occupancy classes for the adjacent units have been updated. Please see sheet A0.1. One hour fire wall to remain. Please see the attached letter from the fire sprinkler contractor." Letter from Fire alarm contractor Ike with Dynamic Security said "sprinkler monitoring fire alarm system in place which also includes the backflow preventers." Since I wasn't sure if a) there was a fire alarm system and there were back flows or if he meant b) the fire alarm monitored the backflow I decided to call Ike. He confirmed that yes the backflow had tampers that are electronically supervised by the fire alarm. 

Plans do show 1 hour separation adjacent mercantile.

3/8/2024 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until  a permit has been pulled :

- Fire sprinkler system

- Kitchen hood (1 type I hoods, wall types shown on A2 (metal studs with gypsum).
- Kitchen suppression system

3/8/2024 VVitori

2) Remove Captive Aire Hood and Suppression pages from this submittal as these will be submitted as sub permits pulled by the respective contractor that will complete the work.

Friday, March 8, 2024 No response to comment. Captive Aire pages not removed. I stamped "NOT PART OF THIS PERMIT"

3/8/2024 VVitori

3) Will CO2 beverage system exceed 100 pounds? If so, demonstrate compliance with NFPA 55:13.11.

NOTE:Make sure to include CO2 tank location, CO2 piping to mixing location (ex- bag/box), indicate which option will be used (ventilation vs sensor/notification) AND show compliance with chosen option of compliance. If Sensor/notification, show locations of the devices.

Friday, March 8, 2024 Response to comment indicates "The CO2 beverage system does not exceed 100 lbs."

3/8/2024 VVitori