SJC Home
Clearance Sheet C2020-007158

 Department IssuesSigned OffIntl

Plan submitted for new Tank overlapping high proximity suppression system protecting a 14' hood with equipment  in a 126"x30" zone (unknown equipment arrangement). Reviewed as using FFPC 8th edition effective January 1, 2024. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

INSPECTOR: Make sure there is no large/industrial fryers over 14" wide, woks larger than 24", appliances with shelves or solid fuel appliance. If there are the plans will need to be resubmitted for review showing how these devices were covered in accord with the manual. (based on page 22 of tank manual).

6/7/2024 RDowling

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

6/7/2024 RDowling

1) Unable to determine how many inches the right nozzle is from the right end of cooking appliance. TANK manual page 22

NOTE: Only dimension shown on the right is 30.99 from right nozzle to right end of hood.

6/7/2024 RDowling