1) Need Notification devices in the following rooms (NFPA 101:9.6.3.5):
Sheet E7.0: Laundry Room 161, Linen Room 162, Staff Break Room 159, Resident Laundry 187, Treatment Room 109, Medical Office 110b,
Sheet E7.1: No notification devices found in the Open Courtyard
Sheet E7.3: No notification devices found in the Open Courtyard
Sheet E7.2: Restroom Room Lobby area 115, 
Sheet E7.3: Mail Center Room 105, Director of Sales 121, Director of Activities 122, Coffee Shop area including Coffee Bar and Internet Caffe rooms 116-117-118 need notification coverage, Resident Laundry 134, Fire Riser / Fire Pump Room 126
Sheet E7.4: Resident Laundry 245, Memory Care Courtyard,
Sheet E7.5: Resident Laundry 226, 
Sheet E7.6: Resident Laundry 247, General Store 249, Corridor 21a, 
Sheet E7.7: Treatment Room 205, Wellness Room 201, Charting and Records 219,