| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for BDA system in new building. Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
5/14/2021
| VVitori |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
5/14/2021
| VVitori |
|
|
1) Do not see where building will be provided with NFPA 780 lightning protection. Main building plans need electrical revision showing building will be protected with NFPA 780 lightning protection. 1221:9.6.3
Friday, May 14, 2021 Response to comments indicates "Drawing for lighting protection will be provided by others (G.C. is working on these electrical drawings."
Letter dated 5 7 21 from PE Tom Elder indicates "In regard to the system as a whole meeting the surge protection requirements for lighting protection, the system design and installation required the roof, the sled mast are isolated from each other and grounded separately. The repeater is to be provided with surge protection which complies with NFPA 780. This configuration demonstrates compliance with NFPA 1221:9.6.3, and NFPA 780.4.20."
|
5/14/2021
| VVitori |
|
|
2) Unable to locate where all repeater, transmitter, receiver, signal booster components, external filters and battery system components will be put in a nema4- or nema4x type enclosure. 1221:9.6.11.2
Friday, May 14, 2021 Response to comments indicates "Repeaters are in are in second floor electrical room. All splitters are shown on the drawing as miscellaneous, on both the first and second floor in Elec room (shown on pg4 & 5). Per repeater spec sheet, repeater is in NEMA 4 enclosure. The battery backup is in the same room as the repeater."
|
5/14/2021
| VVitori |
|
|
Make sure primary power source is supplied from dedicated branch circuit. 1221:9.6.12.1
Friday, May 14, 2021 Response to comment indicates "Electrician to give dedicated 120v outlet to plug into repeater, located in the second floor electrical room."
|
5/14/2021
| VVitori |
|
|
3) Where is the dedicated panel to be located? 1221:9.6.13.2
Friday, May 14, 2021 Response to comment indicates "The panel is located in the electric room in the second floor (shown on the riser pg7)."
|
5/14/2021
| VVitori |
|
|
4) Where is all of 1221:9.6.14 information provided?
Friday, May 14, 2021 Response to comments indicate "See attached specs Frequencies required I. 853.8875 II. 853.7125 III. 853.6375 IV. 853.3875"
|
5/14/2021
| VVitori |