Plan submitted for BDA system in new building. Reviewed using FFPC 7th edition effective January 1, 2021.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1) Do not see where building will be provided with NFPA 780 lightning protection. Main building plans need electrical revision showing building will be protected with NFPA 780 lightning protection. 1221:9.6.3

 

2) Unable to locate where all repeater, transmitter, receiver, signal booster components, external filters and battery system components will be put in a nema4- or nema4x type enclosure. 1221:9.6.11.2

 

Make sure primary power source is supplied from dedicated branch circuit. 1221:9.6.12.1

 

3) Where is the dedicated panel to be located? 1221:9.6.13.2

 

4) Where is all of 1221:9.6.14 information provided?