Plan reviewed for new FM200 system to cover IT computer room. Reviewed using FFPC 7th edition effective January 1, 2021.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

3/24/2021 VVitori

Make sure manual operating device is easily identified as to the hazard it protects. 2001:4.3.3.10

Make sure warning and instruction signs posted at entrance to and inside protected area. 2001:4.3.5.5

Installation approval will need to meet 2001:7.7

3/24/2021 VVitori

Currently abort switch is shown outside of the protected area. 2001:4.3.5.3 requires it to be located within the protected area near the means of egress.

3/24/2021 VVitori