| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for a new aboveground only 218 head nfpa 13 sprinkler system to cover a new building. FDC is showing part of underground (which is not covered in this review). Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
NOTE: asked site Reviewer Murray about her comment regarding no FDC. It was explained that site designer wouldn't indicate or outline underground. Note made indicating that the FDC is not part of the aboveground. I told her that she will need to capture FDC.
|
3/10/2021
| VVitori |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
2/22/2021
| VVitori |
|
|
1) I do not see how the 44 x 77 office pods on the 2nd floor are to be protected. Either show protection or provide reference that allows exemption. 13:8.1.1
Friday, February 12, 2021 Plan page FP3 shows "44 x 77 pods are no longer being installed. per contractor."
Main plans need to be revised to remove the pods.
Monday, February 22, 2021 Received email 2 19 21 from Angelo Group indicating revision for pod removal will be submitted today. I see where the revision has been submitted.
|
2/22/2021
| VVitori |
|
|
2) Several F1FR56 heads (1st floor near draft stop) are 2.5' and 4.5'apart. How will skipping be prevented? 13:8.6.3.4 PageFP1.0 engineer note 2d
Friday, February 12, 2021 It appears some heads moved but concern still exists right side of lobby area open to above (closets to golf simulation suite) there are 2 heads protecting the draft stop within 4.5' of the head on the branch line to its right.
I emailed and called Jeramie at 305p. I offered to hold until end of business Friday Feb. 19th.
Monday, February 22, 2021 Nothing received.
Wednesday, March 10, 2021 Resubmittal included updated image on 8x11.
|
3/10/2021
| VVitori |
|
|
3) EOR (page FP1.0) indicates max head spacing is allowed upto 15'.
1st floor kids zone has 2 at 16'.
1st floor right stair is 15.5'.
Friday, February 12, 2021 Corrected on FP2.
|
2/12/2021
| VVitori |
|
|
4) 2nd floor conference room shows 2 sets of pendant heads in close proximity of each other. Is this to protect above and below a suspended ceiling? If not explain how skipping is to be addressed.
Friday, February 12, 2021 Plan page FP3 updated to show upright and pendant to protect above and below ceiling.
|
2/12/2021
| VVitori |