| | Department Issues | Signed Off | Intl |
|
|
Beau Clark-Whitestone Construction 904-660-2904
Plan approved for 4" DCDA to freestanding FDC to 4" fire sprinkler line to finish 1 ft above finish floor.
|
3/1/2021
| SMurray |
|
|
Fire Dept Connection shall: - 36" clearance in front and side of FDC - Have check valve (NFPA 13) - Have caps in place. (NFPA 24 5.9.1)
|
3/1/2021
| SMurray |
|
|
General Requirements: - Top of the pipe shall be buried not less than 2 1/2 ft to prevent mechanical damage (NFPA 24:10.4.3) - Pipe under driveways shall be buried at a minimum depth of 3 ft (NFPA 24:10.4.4) - All aboveground pipe (including backflow) shall be protected against freezing. (NFPA 24:10.5.1) - Backflow preventer shall be chained and locked unless otherwise required by the Fire or Bldg Code (NFPA 24:6.7.2)
**Pipe being installed is required to be pressure tested. If it is an extension of existing pipe, new pipe must be isolated by a valve or the entire pipe will be required to be pressurized back to the backflow preventer.**
|
3/1/2021
| SMurray |
|
|
To schedule a fire inspection BEFORE cover up of pipe, use the automated system: please call 904-827-6842 press 1, enter building permit 12008469 and enter appropriate code for sprinkler underground visual(638), sprinkler underground hydro(605), sprinkler underground flush(637) OR call 904-209-1740 press 1, then press 2.
INFORMATIONAL: Your permit fee includes the cost of review, one hydrostatic test inspection and one final inspection. If you will require more than one hydro/visual inspection you will need to call 209-1740 x 1 to arrange payment.
|
3/1/2021
| SMurray |