SJC Home
Clearance Sheet C2020-001668*001

 Department IssuesSigned OffIntl

Plan reviewed for renovation of a 1,150 square foot non-sprinklered business occupancy. Renovation to include new flooring, painting and replace existing lighting with recessed can lighting throughout. NO Reconfiguration of space. Reviewed using FFPC 6th edition effective Dec. 31, 2017.    This plan is approved.

Reviewer: D. Feagle 904-209-1721   

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

4/2/2020 dfeagle
INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Existing Emergency lighting in the corridor and lobby as well as the lit exit sign at the front door as indicated on the original building plans (permit 11813696) are to remain.
4/2/2020 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
If occupant sensors (motion activate lighting) is installed, at time of fire final be prepared to show compliance with NFPA 101 7.8.1.2.2:

(1) switch controllers must be listed (2) switch controllers equipped for fail-safe operation and evaluated for this purpose (3)  timers be set for a minimum 15 minute duration. (4)  motion sensor be activated by any occupant movement in the area served by lighting units (5) If building has a fire alarm, activation of fire alarm must activate the switch controller (6)  lighting control device may not turn off any lights realized upon for activation of photo luminescent exit signs or path markers (7) Lighting control devices may not turn off any battery equipped emergency luminaries, unit equipment or exit signs

4/2/2020 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- wall and ceiling finish will meet Class A, B or C. 101:38.3.3.2.2

- floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:38.3.3.3.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

4/2/2020 dfeagle