Clearance Sheet C2020-000462*002

 Department IssuesSigned OffIntl

Plans for a new 24 device non required voice evacuation fire alarm system for the Sheriff guest range house, utilizing a Notifier addressable panel. The alarm is not indicated to be monitored.  The plans are NOT APPROVED as submitted with important comment below.


                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

Visible notification appliances are required in all offices per NFPA 101:9.6.3.5.  Indicate these devices on the plans and update the battery calculations.

 

The plans indicate fire alarm flow switch and tamper switch for a sprinkler system.  The building does not have a fire sprinkler system. Please remove.