Plan REJECTED for remodel of existing 2988 sqft bldg for a vet clinic. This is reviewed under 2007 Fl Fire Prevention Code as business.

*Please label each room as to it's use. Are there to be kennels in the back? Is there to be any office space? How many exam rooms? Any rooms to be used for surgery?

*Will there be any oxygen or x ray machines in use? If so, please label location and show how the walls are being protected for the x ray.

 

If this is light-frame truss-type construction (repetitive wood  members)placement of approved Firefighting Safety Warning Sign (Maltese Cross) shall be placed on structure in accordance with FS 633.027 and FAC 69A-60.008 (size, color, height placement)