Plan reviewed for a new fire alarm system monitoring the sprinkler system only backflow included. The duct smokes are being supervised as well.

FACP= Fire Lite ES-200X, Annunciator, Fire Lite ANN-80. Battery Calculations provided.

The fail safe per plan is NOT being monitored by the Fire alarm.

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.