SJC Home
Clearance Sheet C2009-000036*004

 Department IssuesSigned OffIntl

1. This was a preliminary review. Please resubmit with approved Site Plan and Clearance Sheet.

11/3/2023 jedwards

2. 2020 FBC-Mechanical  606.2 stipulates that a smoke detector must be provided in the supply air duct in systems having a capacity greater than 2,000 cubic feet per minute.

11/3/2023 jedwards

3. Please address Fire Services comment #4.

11/3/2023 jedwards