1. This was a preliminary review. Please resubmit with approved Site Plan and Clearance Sheet.

 

2. 2020 FBC-Mechanical  606.2 stipulates that a smoke detector must be provided in the supply air duct in systems having a capacity greater than 2,000 cubic feet per minute.

 

3. Please address Fire Services comment #4.