SJC Home
Clearance Sheet C2008-002001*008

 Department IssuesSigned OffIntl

Plan reviewed for the addition of 533 SF of New space consisting of storage, public laundry, office/training room, counter and chairs. Type VB construction, Non-Sprinkled, Unprotected, Separated Use.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

---------------------

Friday, November 18, 2022 DF: RTC: Review of 1st Resubmittal. No Response to comments provided.

11/18/2022 dfeagle

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

11/18/2022 dfeagle

1 set of plans for XXX clearance sheets (C2008-002001*007 and C2008-002001*008). This comment will not be signed off until both clearance sheets have all other comments addressed.

11/21/2022 dfeagle

1) Stock Room 20 (storage) is not separated from the mercantile area. 101:36.3.2.1.1.

Demonstrate compliance with 101:8.7.

---------------------

Friday, November 18, 2022 DF: RTC: NO response to comments. Not addressed.

---------------------

Monday, November 21, 2022 0920 hrs. DF: I spoke with Mr. Jack Rymer of Pilot Travel Centers regarding this open comment. After discussing it in detail Mr. Rymer agreed to allow this comment to be submitted as a revision with a Hold 105 Inspection (framing) for the revision submittal.

11/21/2022 dfeagle

2) The new Public Laundry area is not seperated from the mercantile area. 101:36.3.2.1.1

Demonstrate compliance with 101:8.7.

---------------------

Friday, November 18, 2022 DF: RTC: NO response to comments. Not addressed.

---------------------

Monday, November 21, 2022 0920 hrs. DF: I spoke with Mr. Jack Rymer of Pilot Travel Centers regarding this open comment. After discussing it in detail Mr. Rymer agreed to allow this comment to be submitted as a revision with a Hold 105 Inspection (framing) for the revision submittal.

---------------------

Friday, December 2, 2022 DF: I spoke via phone with Dwayne regarding the laundry machines. Per Dwayne they are the size of residential machines that take coins or a card. There will be 3 washers and 3 dryers. 101:36.3.2 does not specifically call out residential style machines and the annex is silent on this type of equipment as hazardous. Based on this the separation requirement is removed.

11/21/2022 dfeagle

3) Need to show the normal and emergency egress lighting in the large dumpster area.

---------------------

Friday, November 18, 2022 DF: RTC: NO response to comments. Not addressed.

---------------------

Monday, November 21, 2022 0920 hrs. DF: I spoke with Mr. Jack Rymer of Pilot Travel Centers regarding this open comment. After discussing it in detail Mr. Rymer agreed to allow this comment to be submitted as a revision with a Hold 105 Inspection (framing) for the revision submittal.

---------------------

Friday, December 2, 2022 DF: I spoke via phone with Dwayne regarding the lighting in the dumpster area. Per Dwayne the parking lot lighting is the normal lighting for this area. No emergency lighting will be required for this area.

11/21/2022 dfeagle

4) Exit signs must match BOTH Electrical page(s) and Life Safety Code page(s).

11/18/2022 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

Occupancy Sensor NFPA 101: 7.8.1.2.2  
Unless prohibited by Chapters 11 through 43, automatic lighting control devices shall be permitted to temporarily turn off the illumination within the means of egress, provided that each lighting control device complies with all of the following:
(1) In new installations, the lighting control device is listed.
(2) The lighting control device is equipped to automatically energize the controlled lights upon loss of normal power and is evaluated for this purpose.
(3) Illumination timers are provided and are set for a minimum 15-minute duration.
(4) The lighting control device is activated by any occupant movement in the area served by the lighting units.
(5) In new installations, the lighting control device is activated by activation of the building fire alarm system, if provided.
(6) The lighting control device does not turn off any lights relied upon for activation of photoluminescent exit signs or path markers.
(7) The lighting control device does not turn off any battery-equipped emergency luminaires, unit equipment, or exit signs.

11/18/2022 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Air handlers with more than 2000 CFM are required to have duct smoke detectors. NOTE: If there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. (NFPA 90A:6.4.4.2)
Where smoke detectors required by 6.4 are installed in a building not equipped with an approved fire alarm system as specified by 6.4.4.2, the following shall occur:
1. Smoke detector activation required by section 6.4 shall cause a visual signal and an audible signal at a normally occupied area.
2. Detector troubles shall be indicated visually or audibly in a normally occupied area identified as air duct

11/18/2022 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:  NFPA 101 7.9.2.3
(1) Failure of a public utility or other outside electrical power supply
(2) Opening of a circuit breaker or fuse
(3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities.
NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2.

11/18/2022 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY: 101:8.3.2.4
Each new Fire Wall, Fire Barrier, Fire Partition, Smoke Barrier, Smoke Partition, or any other new wall required to have protected openings shall be permanently identified with signs or stenciling above any decorative ceiling and in concealed spaces, with the wording “FIRE AND SMOKE BARRIER – PROTECT ALL OPENINGS”, or similar language. Such signs or stenciling shall be 4 in. high letters, ½ in. stroke, and not more than 15 ft. on center.

11/18/2022 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
-
- HOLD 105 INSP: Review Comment #1 - Stockroom Rated Separation
- HOLD 105 INSP: Review Comment #2 - Public Laundry Room Separation 
- HOLD 105 INSP: Review Comment #3 - Large Dumpster Area - Normal Egress lighting AND Emergency Lighting. 
-
-

11/21/2022 dfeagle