Plan APPROVED for 1875 sq ft bldg for haircutting. This was reviewed under 2007 Fl Fire Prevention Code as business.
|
5/20/2009
| SLM |
|
|
FS 633.061 requires a license or permit of organizations & individuals who: service, recharge, test, mark, inspect, install or hydrotest fire extinguishers. It will be necessary to use a Licensed Fire Extinguisher Contractor for identifying the location & type of extinguisher to use.
|
5/20/2009
| SLM |
|
|
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". (NFPA 1, 10.12.1.2)
|
5/20/2009
| SLM |
|
|
All doors that have dead bolts shall use thumb type single cylinder. (NFPA 101, 7.2.1.5)
|
5/20/2009
| SLM |
|
|
The elevation of the floor surface on both sides of a door shall not vary by more than a
1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. (NFPA 101 7.2.1.3)
|
5/20/2009
| SLM |