SJC Home
Clearance Sheet C2006-001397*025

 Department IssuesSigned OffIntl

Plan reviewed for a 2778 SF interior build-out business occupancy expansion; Sprinklered. Reviewed using FFPC 7th edition effective Dec. 31, 2020.

Reviewer: 
Aaron Connell 904-599-8253 aconnell@sjcfl.us 
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

5/1/2023 aConnell

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed.

5/1/2023 aConnell

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:

- Fire sprinkler system

5/1/2023 aConnell

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- Wall and ceiling finish will meet Class A, B or C. 101:38.3.3.2.2

- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:38.3.3.3.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

5/1/2023 aConnell

**INFORMATIONAL ONLY NO RESPONSE NECESSARY:

Verify that all new and existing emergency and exit lighting circuits are tied to the lighting circuit for the area served and un-switched. A direction indicator showing the direction of travel, shall be placed in every location where the direction of travel to reach the nearest exit is not apparent. 101:7.10.2.1 This will be verified at fire final.

5/1/2023 aConnell