| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for interior build out in a 1410sf mercantile occupancy Building is type IIB construction and is protected with an automatic fire sprinkler system. Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: Aaron (Bryan) Connell 904-209-1778 aconnell@sjcfl.us To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
12/21/2023- ABC: Reviewed resubmittal
|
12/21/2023
| aConnell |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 7th Ed.
12/21/2023- ABC: Response to comments submitted.
|
12/21/2023
| aConnell |
|
|
1. Will CO2 beverage system exceed 100 pounds? If so, demonstrate compliance with NFPA 55:13.10.
NOTE:Make sure to include CO2 tank location, CO2 piping to mixing location (ex- bag/box), indicate which option will be used (ventilation vs sensor/notification) AND show compliance with chosen option of compliance. If Sensor/notification, show locations of the devices.
12/21/2023- ABC: Response= Less that 100 pounds
|
12/21/2023
| aConnell |
|
|
2. Exit signs must match BOTH Electrical page(s) and Life Safety page(s).
12/21/2023-ABC: Exit signs match.
|
12/21/2023
| aConnell |
|
|
3. Noted kitchen exhaust hood plans Econ-air Sheets 1-5 were submitted with plan set and clouded notes were made in reference on Sheet G-1. Please label the kitchen exhaust hood plan Sheets 1-5 "For Reference Only."
12/21/2023- ABC: Hood pages now state for reference only
|
12/21/2023
| aConnell |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- Fire sprinkler system - Kitchen hood - Kitchen suppression system
|
12/21/2023
| aConnell |
|
|
**INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Verify that the existing emergency and exit lighting circuit is tied to the lighting circuit for the area served and un-switched. This will be verified at final.
|
12/21/2023
| aConnell |