The submitted plans are for two detached structures as well as a porch addition to the main house. Each of these projects require a separate permit application although you will be able to use a single set of plans for permitting.
|
7/18/2023
| tfitz |
|
|
It appears manufactured trusses will be used for the two accessory buildings and therefore will require shop drawings by a truss company that have been reviewed by the design professional of record for this project.
|
7/18/2023
| tfitz |
|
|
It is unclear whether the energy calculations provided are for the new office or the enclosure of the existing porch, please clarify. They also lack a manual "D" indicating supply sizing and duct layout.
|
7/18/2023
| tfitz |
|
|
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
|
7/18/2023
| tfitz |