317.1Location required.
Protection of wood and wood-based products from decay shall be provided in the following locations by the use of naturally durable wood or wood that is preservative-treated in accordance with AWPA U1.
-
1.Wood joists or the bottom of a wood structural floor when closer than 18 inches (457 mm) or wood girders when closer than 12 inches (305 mm) to the exposed ground in crawl spaces or unexcavated area located within the periphery of the building foundation.
-
2.Wood framing members that rest on concrete or masonry exterior foundation walls and are less than 8 inches (203 mm) from the exposed ground.
-
3.Sills and sleepers on a concrete or masonry slab that is in direct contact with the ground unless separated from such slab by an impervious moisture barrier.
-
4.The ends of wood girders entering exterior masonry or concrete walls having clearances of less than 1/2 inch (12.7 mm) on tops, sides and ends.
-
5.Wood siding, sheathing and wall framing on the exterior of a building having a clearance of less than 6 inches (152 mm) from the ground or less than 2 inches (51 mm) measured vertically from concrete steps, porch slabs, patio slabs and similar horizontal surfaces exposed to the weather.
-
6.Wood structural members supporting moisture-permeable floors or roofs that are exposed to the weather, such as concrete or masonry slabs, unless separated from such floors or roofs by an impervious moisture barrier.
-
7.Wood furring strips or other wood framing members attached directly to the interior of exterior masonry walls or concrete walls below grade except where an approved vapor retarder is applied between the wall and the furring strips or framing members
WALLS THAT WHERE CONSTRUCTED PRIOR TO PERMITING ARE NOT IN ACCORDANCE WITH CODE . PLEASE REFER TO NUMBER 5 THIS INCLUDES FRAMING ,OSB AND SIDING
|
| |
|
|
WALLS CONSTRUCTED BEFORE PERMITING DO NOT SHOW J BOLTS AND ALL THREAD,PLEASE PROVIDE DETAIL ON FRAMING ATTACHMENT TO EXISTING WALLS,FLOORS,AND HEADERS.
|
| |
|
|
DETAIL PROVIDED SHOW ZIP WALL SYSTEM THIS IS NOT APPARENTLY USED IN THE WALLS CONSTRUCTED BEFORE ISSUANCE OF PERMIT
|
| |