SJC Home
Clearance Sheet R2021-007775

 Department IssuesSigned OffIntl

1. The Architectural drawings do not appear to match the Structural engineering. Please review and submit matching drawings.

ADDED ON 12/16/2021; The New Engineering is designed to the 2017 FBC-R. Please submit 2020 FBC-R designs.

 

2. It appears the local utility company doesn't provide Sewer service to this property. Please show septic sewer system on the SJC approved site-plan.

ADDED ON 12/16/2021; Item not addressed.

 

3. Please submit the Florida Environmental Health Sewer septic System permit with the floor plan and site-plan.

ADDED ON 12/16/2021; Item not addressed.

 

4. As per 2020 FBC-R section 310, it appears the windows for the master bedroom will not meet the code requirement of 20 inch net clear width.

R310.2.1Minimum opening area.

Emergency and escape rescue openings shall have a net clear opening of not less than 5.7 square feet (0.530 m2). The net clear opening dimensions required by this section shall be obtained by the normal operation of the emergency escape and rescue opening from the inside. The net clear height opening shall be not less than 24 inches (610 mm) and the net clear width shall be not less than 20 inches (508 mm).

 

Please review the Window Manufacturer (MI) cut sheets for model #9770 Casement window. It appears the net clear width for the 2 foot wide window series is just over 16 inches.

12/16/2021 jdacosta
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
 
Pen and ink changes, white-outs, or any such altering of raised seal engineering drawings, is not permitted under state laws governing the practice of Architecture or Engineering. All information on the raised seal drawings must part of the printed sheets at the time the drawings are sealed by the Architect/Engineer.