| | Department Issues | Signed Off | Intl |
|
|
1. Unable to verify roof sheathing thickness. Sheet Ss-6 indicates 7/16 while stating metal may require more stringent sheathing. Please provide the Product Approval number for metal roof cover being used to confirm roof sheathing thickness required.
|
6/29/2021
| jdacosta |
|
|
2. This project is located in the Wind-Borne Debris Region. As such, plans must include provisions for protection of openings per 2020 FBC-Building Section R301.2.1.2. Please identify opening protection being used.
ITEM ADDED ON 06/29/2021; Item not fully addressed. Please provide the Florida Product Approval numbers for Impact rated windows, and doors if applicable.
|
7/28/2021
| jdacosta |
|
|
3. Please provide the Testing Agency approved affidavit for the spray foam insulation being used.
|
6/29/2021
| jdacosta |
|
|
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
|
7/28/2021
| jdacosta |
|
|
Pen and ink changes, white-outs, or any such altering of raised seal engineering drawings, is not permitted under state laws governing the practice of Architecture or Engineering. All information on the raised seal drawings must part of the printed sheets at the time the drawings are sealed by the Architect/Engineer.
|
7/28/2021
| jdacosta |