SJC Home
Clearance Sheet R2021-000951*004

 Department IssuesSigned OffIntl

1. The structural plans submitted are designed to the 2020 Building Code. The current code cycle is 2023.

---Please update and resubmit plans designed to the 2023 Building Code.

Plans were submitted conditionally prior to 2024 

1/26/2024 janoda

2. Based on the site plan and the drawings submitted the wall of the structure is located 3 feet from the property line. The eve overhang is going to be less than 3 feet to the property line.

Florida Building Code R302 requires projections less than 3 feet to the property line be 1hr fire rated and less than 2 feet is not allowed.

--- To satisfy the requirement of the FBC R302 the eve next to the property would need to be less than a 12" overhang and be fire rated to 1 hour.

---Please address this issue with your designer.

 

2/8/2024 janoda

3. Please provide note on plan requiring 5/8" Type X Gypsum on the ceiling of the garage per Florida Building Code R302.6

2/8/2024 janoda

4. The clearance sheet specifies 8 foot side setback the site plan shows 3 foot setback.

--- Please readdress this with Planning and Zoning.